| Plan Review Notes For Permit 04100287 |
| Permit Number |
04100287 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-11-24 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) AIR CHAMBERS ARE NOT APPROVED. | | | DELETE | | | FROM WATER RISER DIAGRAM. WATER HAMMER | | | ARRESTORS REQUIRED BY SECTION 604.9 | | | SHALL BE LOCATED NEAR THE FIXTURE NOT | | | IN | | | THE CEILING. PDI-WH 201 AND MANUF. | | | INSTALLATION INSTRUCTIONS. | | | 2) REMOVE ALL VOIDED SHEETS AND SUBMIT 2 | | | SETS OF PLANS FOR REVIEW. SUBMIT 1 | | | VOIDED SET OF SHEETS SEPARATELY FOR | | | COMPAIRISON. SECTION 104.2.1 | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|