| Plan Review Notes For Permit 04100187 |
| Permit Number |
04100187 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-10-20 00:00:00 | 1) PLEASE INDICATE INTERIOR FINISH | | | THAT WILL BE USED ON NEW WALLS. | | | | | | 2) THE 5TH FLOOR SHOWS ONLY ONE | | | FIRE EXTINGUISHER. TRAVEL DISTANCE | | | TO REACH A FIRE EXTINGUISHER SHALL | | | NOT EXCEED 75 FEET. | | | | | | 3) PLEASE SUBMIT SHOP DRAWINGS FOR | | | FIRE SPRINKLER REMODEL. | | | | | | 4) PLEASE SUBMIT SHOP DRAWINGS FOR | | | FIRE ALARM REMODEL. | | | | | | 5) ARE THERE ANY UL DOOR CLOSERS AND | | | HARDWARE ON THE RATED FIRE DOORS. | | | | | | MIKE WENNERGREN, LIEUTENANT | | | 835-2950 |
|