| Plan Review Notes For Permit 04100184 |
| Permit Number |
04100184 |
|
| Review Stop |
B |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2005-10-06 00:00:00 | BUILDING SUBMITTAL CHECKLIST: | | | 1- STORM SHUTTERS KEY PLAN SHOWS THAT | | | EMERGENCY EGRESS DOOR IS LOCATED IN THE | | | GARAGE. THIS IS NOT ALLOWED BY SECTION | | | 1005.4.5 FBC 2001. NEED TO PROVIDE | | | EMERGENCY EGRESS THAT SATISFY CODE | | | SECTION CITED ABOVE. REVISE INSTALLATION | | | SCHEDULE AND KEY PLAN AS REQUIRED. | | | | | | 2- HAND WRITTEN NOTES ON SHEET 5 OF 7 OF | | | SHUTTERS DRAWINGS DON'T MATCH DIMENSIONS | | | SHOWN ON THE INSTALLATION SCHEDULE. | | | REVISE AS REQUIRED. | | | | | | 3- CONTRACTOR NEEDS TO UPDATE THE | | | LICENSE AND WORKERS COMPENSATION WITH | | | THE CLERKS AT THE FRONT COUNTER. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712. |
|