| Plan Review Notes For Permit 04100184 |
| Permit Number |
04100184 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-12-13 00:00:00 | BUILDING REVIEW PROVISO: | | | 1-SPECIFY ON PLANS SIZE OF CEILING | | | FANS SINCE CREDIT WAS TAKEN ON THE | | | ENERGY CALCULATIONS FOR CEILING FANS. | | | SEE TABLE 6-6 CHAPTER 13 FBC 2001. | | | | | | 2-PROVIDE FLORIDA PRODUCT APPROVAL FOR | | | GARAGE DOORS WITH SAME REPORT & DWGS | | | SUBMITTED TO FLORIDA BUILDING | | | COMMISSION FOR REVIEW AND APPROVAL. | | | | | | 3-PROVIDE FLORIDA PRODUCT APPROVAL FOR | | | STORM SHUTTERS WITH SAME DRAWINGS THAT | | | WERE SUBMITTED TO FLORIDA BUILDING | | | COMMISSION FOR REVIEW AND APPROVAL. | | | **ALSO, CLEARLY INDICATE ON SHUTTER | | | DWGS SPECIFIC MOUNTING CONDITIONS AND | | | ANCHOR TYPE AND SPACING TO BE USED | | | ACCORDING TO THE DESIGN PRESSURES, EDGE | | | DISTANCE, PANEL SPAN, CONNECTION TYPE | | | AND STRUCTURE TO BE ATTACHED TO (MASONRY | | | OR CONCRETE). | | | | | | 4-FLOOD ZONE A7: NEED TO PROVIDE THE | | | ELEVATION CERTIFICATE. |
|