| Plan Review Notes For Permit 04100184 |
| Permit Number |
04100184 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-10-21 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE NOTE THE BATH CIRCUITS ON THE | | | PANEL SCHEDULE MUST COMPLY WITH | | | 210.11(C)(3), 20AMP #12 WIRE. | | | | | | 2} SPACING OF THE BATH RECEPTACLES MUST | | | COMPLY WITH 210.52(D). SEE MASTER BATH. | | | | | | 3} PLEASE CHECK KITCHEN RECEPTACLE | | | SPACING. MUST COMPLY WITH 210.52(C). | | | | | | 4} PLEASE CHECK ALL RECEPTACLE SPACING | | | FOR COMPLIANCE WITH 210.52 (A). SEE | | | MASTER BEDROOM WALL ADJACENT TO DOOR. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|