| 2004-10-12 00:00:00 | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING |
| | INSTALLED. MAINS/BRKRS AND PANELS ARE |
| | ALL TO BE RATED FOR THE AVAILABLE FAULT |
| | CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 2} SHOW ALL CONDUIT AND CONDUCTOR SIZES |
| | ON THE RISER DIAGRAM, INCLUDING FROM THE |
| | DISCONNECTS TO THE PANELS. |
| | |
| | 3}THERE'S A NEW PANEL SHOWN ON THE PLAN, |
| | PLEASE INCLUDE ON THE RISER WITH FEEDS |
| | AND GROUNDING. |
| | |
| | 4} PROVIDE A PANEL SCHEDULE FOR THE UNIT |
| | BEING REWIRED. |
| | |
| | 5} LABEL ALL ROOMS ON THE PLAN. |
| | |
| | 6} SMOKE DETECTORS ARE REQUIRED PER 8-1. |
| | 4.1.6 NFPA-72 AND 905.2.2 FBC. |
| | |
| | 7} PLEASE SHOW ALL RECEPTS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI |
| | PROTECTED PER 210.8A-6 |
| | |
| | 8} PLEASE LIST ALL THE REQ'D |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | |
| | 9} PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | |
| | 10} PLEASE SEE MISSING RECEPTS FOR |
| | FRONT AND/OR REAR OF DWELLING. |
| | 210.52E |
| | |
| | 11} PLEASE SEE MISSING RECEPT REQ'D |
| | FOR A/C EQUIPMENT. 210.63. SHOW LOCATION |
| | OF EQUIPMENT ON THE PLAN AND |
| | DISCONNECTING MEANS. |
| | |
| | 12} PLEASE COMPLETE THE APPLICATION, THE |
| | OWNER INFORMATION IS MISSING. |
| | |
| | ALL INFORMATION/DRAWINGS/SPECIFICATIONS |
| | AND ACCOMPANYING DATA SHALL BEAR THE |
| | NAME AND SIGNATURE OF THE PERSON |
| | RESPON-SIBLE FOR THE DESIGN. SECTION |
| | 104.2.1 |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |