| 2004-10-25 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) SUBMIT A SANITARY RISER DIAGRAM SHOW- | | | ING EXISTING RISER FOR LAV. SHOW HOW THE | | | RISER FOR THE LAV IS BEING REROUTED. - | | | SHOW HOW LAV WILL BE CONNECTED INTO THE | | | EXISTING SANITARY. SECTIONS 104.2.1 AND | | | 104.3.1.1 | | | 2) INDICATE DIMENSIONS OF POWDER ROOM. | | | 3) SHT MEP-2 PLUMBING NOTES: | | | #5 AIR CHAMBERS ARE NOT APPROVED. DELE- | | | TE FROM REFERENCE. SECTION 604.9 | | | #6 2-1/2" PIPE AND SMALLER SHAL SLOPE | | | 1/4" PER FOOT. TABLE 704.1 - CORRECT | | | THE NOTE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|