| 2004-10-08 00:00:00 | ******* UNSAT ******** |
| | |
| | **PLANS ONLY IN FOR "PLAN REVIEW"**** |
| | |
| | 1)NOTE: PLEASE SEE A NEW WATERFALL |
| | DETAIL IS SHOWN ON A-SHEETSYET THIS |
| | DOES NOT APPEAR ON ELECTRICAL PLANS?? |
| | PLEASE SUBMIT INFORMATION FOR NEW PUMP, |
| | CONNECTION ETC. |
| | |
| | 2)NOTE: PLEASE SEE 210.52C3-5 FOR RECEPT |
| | 'S ALONG PENINSULAR COUNTERSPACE. |
| | |
| | 3)NOTE: PLEASE SEE 210.52 FOR NEW LOFT |
| | AREA AND WALL ADJACENT TO NEW LOFT. |
| | PLEASE INDICATE CIRCUITS/ PANEL. |
| | |
| | 4)NOTE: PLEASE SEE NOTE # 27 MENTIONS |
| | ROMEX PERMITTED BY OWNER OR ARCH. |
| | PLEASE SEE 2002 NEC 334.12. ROMEX NMC |
| | IS NOT PERMITTED IN THIS BLDG DUE TO |
| | TYPE 1 AND TYPE 2 CONSTRUCTION. |
| | |
| | 5)NOTE: PLEASE SEE NOTE #28 MENTIONS |
| | SD'S TO WIRED TO KITCHEN/BATH CIRCUITS. |
| | PLEASE SEE 2002 210.12, THIS WOULD |
| | REQUIRE ARC FAULT ON THOSE CIRCUITS ALSO |
| | PLEASE SEE NFPA-72 8-1.4.6.1.2 FOR |
| | POSSIBLE SD REQUIRED IN LOFT AREA. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |