Plan Review Notes
Plan Review Notes For Permit 04100178
Permit Number 04100178
Review Stop B
Sequence Number 1
Notes
Date Text
2004-10-26 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) WORKING DRAWING REVIEW ONLY.NO
 PERMIT CAN BE ISSUED UNTIL THE PERMIT
 APPLICATION AND FEES ARE SUBMITTED.
  
 2) 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 3) 481.213 F.S.ARCHITECT'S LICENSE.A
 SEARCH ON THE DEPARTMENT OF BUSINESS AND
 PROFESSIONAL REGULATION WEBSITE SHOWED
 THAT DAVID SER'S ARCHITECT'S LICENSE
 (AR0014739) IS DELINQUENT.NO PERMIT
 CAN BE ISSUED FOR THESE PLANS UNTIL THIS
 IS RECTIFIED.
  
 4) FBC 603STRUCTURAL MEMBERS IN TYPE I
 CONSTRUCTION.SHEETS A-3 AND A-4 SHOW
 WOOD 'LOFT' FLOOR AND STAIR TREAD
 CONSTRUCTION.ALL STRUCTURAL MEMBERS
 SHALL BE OF NON-COMBUSTIBLE MATERIALS.
 AMEND THE PLANS.
  
 5) FBC 104.2.1THE PLANS SHALL DETAIL
 (OR STATE "SUBMIT SHOP DRAWINGS" FOR)
 THE MEANS OF ATTACHMENT FOR THE TEMPERED
 GLASS BALUSTRADE, THE CONNECTION BETWEEN
 EACH STAIR TREAD AND IT'S WIRE HANGERS,
 MEANS OF ATTACHMENT FOR THE HANDRAIL.
 SEE ALSO, COMMENT 4 ABOVE.
  
 6) FBC 1608.2.2THE GUARDRAIL SHALL BE
 DESIGNED AND CONSTRUCTED FOR A
 CONCENTRATED LOAD OF 200 LB APPLIED IN
 ANY DIRECTION AT THE TOP OF THE
 GUARDRAIL, A CONCENTRATED HORIZONTAL
 LOAD OF 200 LB APPLIED ON A 1 SQ FT AREA
 AT ANY POINT, AND A LINE LOAD OF 50 PLF
 APPLIED HORIZONTALLY AT THE REQUIRED
 GUARDRAIL HEIGHT WITH A SIMULTANEOUS
 LINE LOAD OF 100 PLF APPLIED VERTICALLY
 DOWNWARD ON THE TOP OF THE GUARDRAIL.
 THESE LOADS SHALL NOT BE APPLIED
 SIMULTANEOUSLY (UNLESS NOTED ABOVE) BUT
 SHALL BE APPLIED INDIVIDUALLY TO PRODUCE
 MAXIMUM STRESS IN EACH OF THE COMPONENTS
 OR SUPPORTS.AMEND/ANNOTATE THE PLANS.
  
 7) FBC 1608.2.1THE HANDRAIL SHALL BE
 DESIGNED AND CONSTRUCTED FOR A
 CONCENTRATED LOAD OF 200 LB AND A LINE
 LOAD OF 50 PLF.THESE LOADS SHALL NOT
 BE APPLIED SIMULTANEOUSLY BUT SHALL BE
 APPLIED INDIVIDUALLY AT ANY POINT, AND
 IN ANY DIRECTION, TO PRODUCE MAXIMUM
 STRESS IN EACH OF THE COMPONENTS OR
 SUPPORTS.AMEND/ANNOTATE THE PLANS.
  
 8) TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS, TO FORM A SET OF
 'OLD/VOID SHEETS', FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE RESUBMITTED
 PLANS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]