| Plan Review Notes For Permit 04100155 |
| Permit Number |
04100155 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-01-11 00:00:00 | | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} INDICATE THE SIZE AND TYPE OF THE | | | CONDUIT AND CONDUCTORS IN THE | | | "EXISTING" | | | RISER. | | | | | | 2} FURNISH A LOAD CALCULATION FOR THE | | | HOUSE PANEL, ADD SAME TO UNIT CALCS. | | | | | | 3} THE DESIGNER OF RECORD MUST PRINT AND | | | SIGN THE PLANS PER 104.2.1 FBC. THIS | | | COMMENT WAS ON THE PEVIOUS REVIEW. IF | | | THERE ARE QUESTIONS PLEASE CALL. | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|