Plan Review Notes
Plan Review Notes For Permit 04100155
Permit Number 04100155
Review Stop E
Sequence Number 2
Notes
Date Text
2004-12-21 00:00:00 
 HAND DRAWN CHANGES TO THE PLAN ARE
 UNACCEPTABLE. THE PLANS CAN ONLY BE
 REVISED BY THE DESIGNER OF RECORD AND
 SHALL CONTAIN THE PRINTED NAME AND
 SIGNATURE OF SAME PER FBC 104.2.1.
  
 REMOVE ALL DIAGRAMS FROM THE PLAN THAT
 ARE NOT TO BE USED. ALSO THE TERM
 "OPTIONAL "REFERENCING THE GUTTER IS
 NOTACCEPTABLE. IF IT IS NOT TO BE
 INSTALLEDREMOVE IT FROM THE PLAN. SEE
 AN
 ELECTRICAL CONTRACTOR OR ENGINEER IF
 UNCLEAR ON SETTING UP THE SERVICE.
  
 INDICATE WHICH ARTICLES ARE BEING USED
 FOR CALCULATIONS. SEE 220.32.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026