2005-01-11 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER-11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A) FROM PREVIOUS REVIEW:
 2) SHT A-1 SHOW CLEAR FLOOR SPACE THE
 W/C AND THE LAV ON THE FLOOR PLAN
 REQUIRED IN SECTION 11-4.16.2, AND
 11-4.19.3. ALSO SEE SECTION 11-4.22.3.
 RESPONSE NOTED, BUT THE TURNING AREA AND
 THE CLEAR FLOOR SPACE ARE NOT THE SAME.
 SEE FIGS. 28, & 32.
 7) THE PRINTED NAME OF THE PERSON
 SEALING THE DOCUMENT IS REQUIRED PER FAC
 61G1-16.004(6) & FS 481.2055. RESPONSE
 NOTED, BUT NO TITLE BLOCK IS SHOWN AT
 THIS TIME. ARCHITECTURAL TITLE BLOCK
 MUST APPEAR ON ALL ARCHITECTURAL
 DRAWINGS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING
 INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE
 NUMBER.
 (2) FIRM LICENSE NUMBER.
 (4) DATE PREPARED.
 (6) A SPACE FOR THE PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENT.
 *******NEW COMMENT******
 1B) A PROFESSIONAL ENGINEER SHALL SIGN
 HIS NAME AND AFFIX HIS SEAL TO ALL
 PLANS. INITIALS ARE NOT APPROVED. IF
 INDEED THIS IS ENGINEERS LEGAL SIGNATURE
 THEN PLEASE SUBMIT A SIGNED, SEALED,
 DATED, NOTORIZED LETTER INDICATING THIS
 AS A LEGAL SIGNATURE. THE DATE THAT THE
 SIGNATURE AND SEAL IS AFFIXED AS
 PROVIDED HEREIN SHALL BE ENTERED ON SAID
 PLANS. ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESS, AND LICENSE NUMBER
 ON EACH SHEET. 61G15-23.002(1)(2) AND FS
 471.025.
  
  