Plan Review Notes
Plan Review Notes For Permit 04100148
Permit Number 04100148
Review Stop P
Sequence Number 1
Notes
Date Text
2004-10-25 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SUBMIT TWO SETS OF PLANS FOR REVIEW.
 SETS SUBMITTED HAVE LOOSE SHEETS NOT
 ATTACHED TO SET OF PLANS. SEC 104.2.1
 2) SHT A-1 SHOW CLEAR FLOOR SPACE FOR
 THE W/C AND LAV ON FLOOR PLAN AS REQUIR-
 ED IN SECTION 11-4.16.2, AND 11-4.19.3.
 ALSO SEE SECTION 11-4.22.3
 3) SHT A-1 SHOW W/C TO BE 18" FROM WALL
 TO CENTER OF FIXTURE AND LAV TO BE MINI-
 MUM FROM WALL TO CENTER OF FIXTURE. SEC
 104.2.1, FIGURE 28, & FIGURE 32.
 4) SHT M-3 WATER HEATER DETAIL SHOWS THE
 PAN DRAIN TO FLOOR DRAIN. FLOOR DRAINS
 ARE NOT AN APPROVED INDIRECT WASTE REC-
 EPTOR. THE T&P RELIEF VALVE MAY DRAIN TO
 THE EMERGENCY PAN, AND THE PAN DRAIN MAY
 DRAIN TO THE MOP SINK WITH AN AIR GAP.
 SECTION 802.3
 5) SHT M-3 WATER RISER DIAGRAM, WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR
 THE FIXTURES IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING AS SHOWN. PDI-WH 201 AND
 MANUF. INSTALLATION INSTRUCTIONS.
 6) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE. BACKFLOW SHALL BE MAXIMUM
 4' ABOVE THE FLOOR FOR SERVICE AND CERT-
 IFICATION. SECTION 608.13.2
 7) THE PRINTED NAME OF THE PERSON SEAL-
 ING THE DOCUMENT IS REQUIRED PER FAC
 61G1-16.004(6) - FS481.2055
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]