| Date |
Text |
| 2004-10-25 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1) SUBMIT TWO SETS OF PLANS FOR REVIEW. |
| | SETS SUBMITTED HAVE LOOSE SHEETS NOT |
| | ATTACHED TO SET OF PLANS. SEC 104.2.1 |
| | 2) SHT A-1 SHOW CLEAR FLOOR SPACE FOR |
| | THE W/C AND LAV ON FLOOR PLAN AS REQUIR- |
| | ED IN SECTION 11-4.16.2, AND 11-4.19.3. |
| | ALSO SEE SECTION 11-4.22.3 |
| | 3) SHT A-1 SHOW W/C TO BE 18" FROM WALL |
| | TO CENTER OF FIXTURE AND LAV TO BE MINI- |
| | MUM FROM WALL TO CENTER OF FIXTURE. SEC |
| | 104.2.1, FIGURE 28, & FIGURE 32. |
| | 4) SHT M-3 WATER HEATER DETAIL SHOWS THE |
| | PAN DRAIN TO FLOOR DRAIN. FLOOR DRAINS |
| | ARE NOT AN APPROVED INDIRECT WASTE REC- |
| | EPTOR. THE T&P RELIEF VALVE MAY DRAIN TO |
| | THE EMERGENCY PAN, AND THE PAN DRAIN MAY |
| | DRAIN TO THE MOP SINK WITH AN AIR GAP. |
| | SECTION 802.3 |
| | 5) SHT M-3 WATER RISER DIAGRAM, WATER |
| | HAMMER ARRESTORS SHALL BE LOCATED NEAR |
| | THE FIXTURES IN AN "EFFECTIVE RANGE" NOT |
| | IN THE CEILING AS SHOWN. PDI-WH 201 AND |
| | MANUF. INSTALLATION INSTRUCTIONS. |
| | 6) AN RPZ BACKFLOW IS REQUIRED ON THE |
| | WATER SERVICE. BACKFLOW SHALL BE MAXIMUM |
| | 4' ABOVE THE FLOOR FOR SERVICE AND CERT- |
| | IFICATION. SECTION 608.13.2 |
| | 7) THE PRINTED NAME OF THE PERSON SEAL- |
| | ING THE DOCUMENT IS REQUIRED PER FAC |
| | 61G1-16.004(6) - FS481.2055 |
| | |