| Plan Review Notes For Permit 04100148 |
| Permit Number |
04100148 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-10-08 00:00:00 | ********* UNSAT ********** | | | | | | *** PLANS ARE ONLY IN FOR "PLAN REVIEW" | | | AT THIS TIME. *** | | | | | | 1)NOTE: PLEASE SEE FAC 61G1-16.004 FOR | | | ALL REQUIRED INFORMATION IN TITLE BLOCK | | | FOR ARCH. PLEASE INCLUDE PRINTED LIC. # | | | | | | 2)NOTE: PLEASE SEE NOTE FOR TRACK LIGHT- | | | -ING LOAD (PER 220.12) IS SHOWN ON 277/ | | | /480V PANEL? HOWEVER, TRKS LTS ARE | | | SHOWN ON 120/208V PANEL "B". | | | PLEASE VERIFY. | | | | | | 3)NOTE: PLEASE IDENTIFY CIRCUIT # B-2 | | | ON PANEL SCHEDULE AS "SHOW WINDOW RECEPT | | | -S". | | | IT WAS NOTED ON 277/480 LOAD SUMMARY. | | | | | | 4)NOTE: PLEASE PROVIDE WIRING FOR THE | | | "LIGHT-STAT" PANEL AS SHWON ON RISER. | | | RISER SHOWS THIS PANEL BEING WIRED INTO | | | BOTH PANEL "A" AND PANEL "B" WHICH ARE | | | TWO DIFFERENT VOLTAGES?? PLEASE CLARIFY. | | | | | | *** PLANS REFERENCE OLDER CODES FOR | | | OTHER TRADES. JUST A NOTE, WE ARE UNDER | | | THE 2002 NEC. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|