2005-01-10 00:00:00PROVISO:
 1.RETURN AIR JUMPER FROM THE MASTER
 SUITE SHALL BE A MINIMUM OF 12" PER 2001
 FBC(M)601.4 EXCEPTION #1 & 3.
  
 2.A MINIMUM OF 4" AROUND THE AHU IS
 REQUIRED PER 2001 FBC(M)603.1.3.
  
 3.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  