| 2005-01-18 00:00:00 | 3RDCHECKLIST: |
| | 1- ENERGY CALCULATIONS: A) OWNER/AGENT |
| | TO SIGN & DATE BOTTOM OF FORM. ALSO, |
| | PERSON WHO PREPARED THE ENERGY CALCS |
| | NEED TO DATE THEM AS WELL. |
| | |
| | B) REVISE UNDER ATTIC AREA. SEE SECTION |
| | 604.1.A.1 CHAPTER 13 FBC 2001. |
| | |
| | C) COMPLETE INFORMATION ON TOP OF FORM: |
| | ADDRESS, OWNER, BUILDER, PERMIT OFFICE, |
| | ETC. |
| | |
| | 2- SOIL TEST REPORT: A) RECOMMENDS 24" |
| | MIN. WIDTH OF FOOTING AND BOTTOM OF |
| | FOOTING TO BE AT LEAST 18" BELOW GRADE |
| | (SEE PAGE 4). PLANS SUBMITTED SPECIFIES |
| | 18" WIDE FOOTINGS AND THEY ARE ONLY 12" |
| | BELOW GRADE. CLARIFY WHICH ONE HAS THE |
| | CORRECT SPECIFICATIONS AND REVISE AS |
| | REQUIRED TO MATCH. SEC. 104.2.1.2 CITY |
| | AMENDEMNTS TO FBC 2001. |
| | |
| | B)SOIL TEST REPORT NEED TO HAVE |
| | ORIGINAL |
| | SEAL, SIGNATURE AND DATE AS REQUIRED BY |
| | CHAPTER 471 FL. STATUTES WHEN |
| | SUBMITTING |
| | DOCUMENTS FOR PUBLIC RECORDS. |
| | |
| | 3- PROVIDE COMPLETE FLORIDA PRODUCT |
| | APPROVAL (NOTE: DADE COUNTY NOA'S ARE |
| | NOT STATEWIDE PRODUCT APPROVALS. |
| | FLORIDA |
| | PRODUCT APPROVALS ARE) OR APPLY FOR |
| | LOCAL PRODUCT FOR: |
| | A) GLASS BLOCK. |
| | B) "INSWING" ENTRY DOOR. |
| | C) FRENCH DOORS WITH LEGIBLE DRAWINGS. |
| | D) SINGLE HUNG WINDOWS W/ LEGIBLE DWGS. |
| | E) GARAGE DOOR(NOTE: SUBMIT ONLY ONE |
| | DOOR TYPE. THERE WERE 2 DIFFERENT DOORS |
| | SUBMITTED). |
| | F) "OUTSWING" STEEL DOOR. (MECH. RM). |
| | G) ROOF TILE. |
| | H) SIMPSON OR USP STRUCTURAL |
| | CONNECTORS. |
| | I) HORIZONTAL SLIDING WINDOWS. |
| | K) WINDOW MULLIONS. |
| | |
| | 4- SURVEY IS NOT VALID WITHOUT ORIGINAL |
| | SIGNATURE, SEAL AND DATE, WHEN |
| | SUBMITTING FOR PUBLIC RECORDS. |
| | |
| | 5- PROVIDE COMPLETE INFORMATION FOR |
| | STORM SHUTTERS, INCLUDING FLORIDA OR |
| | LOCAL PRODUCT APPROVAL, KEY PLAN AND |
| | COMPLETE INSTALLATION SCHEDULE. SEE |
| | ATTACHED SAMPLE. OR APPLY FOR A |
| | SEPARATE |
| | PERMIT. |
| | |
| | 6-PROVIDE 2X STRUCTURAL BUCK DETAIL FOR |
| | ENTRY AND MECHANICAL ROOM DOORS AS |
| | REQUIRED ON INFORMATION SUBMITTED FOR |
| | DOOR TO BE USED. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |