Plan Review Notes
Plan Review Notes For Permit 04100136
Permit Number 04100136
Review Stop P
Sequence Number 2
Notes
Date Text
2004-11-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUBING
 FBC-2001 CHAPTER 1
  
 1) SHT A-9 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE, NOR DOES IS REFLECT THE
 FLOOR PLAN.
 A) THE WASH MACHINE AND LAUNDRY SINK
 SHALL NOT DRAIN THROUGH THE HORIZONTAL
 WET VENT OF THE BATHROOM FIXTURES.
 SECTION 909.1
  
 SEE ATTACHED SHEET TO SEE AN EXAMPLE OF
 A RISER DIAGRAM THAT REFLECTS THE FLOOR
 PLAN AND MEETS THE CODE REQUIREMENTS.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]