| Plan Review Notes For Permit 04100136 |
| Permit Number |
04100136 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-11-18 00:00:00 | | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE RISER DIAGRAM SHOWS THE 100AMP | | | PANEL FEEDING THE PANEL MARKED 250, THE | | | PANEL SCHEDULE INDICATES THIS AS 200 | | | AMPS, AND NO FEED FROM EITHER PANEL TO | | | THE OTHER IS SHOWN. | | | | | | 2} BOTH PANELS ARE BOTTOM FED, PLEASE | | | CLARIFY, SEE RISER. | | | | | | 3} SHOW CONDUCTOR SIZE, CONDUIT SIZE AND | | | OCP FOR THE FEED BETWEEN PANELS. | | | | | | 4} PLEASE DRAW THE LOCATION OF THE MAIN | | | DISCONNECT ON THE PLAN. | | | | | | 5} THERE IS ONLY ONE SMALL APPLIANCE | | | CIRCUIT ON THE SCHEDULE, THE CALC LISTS | | | 3, PLEASE CORRELATE. | | | | | | 6} THE BATH CIRCUITS LISTED ON THE | | | SCHEDULE@15 AMPS DO NOT COMPLY WITH | | | 210.11(C)(3),20AMP. | | | | | | 7} A SMOKE DETECTOR IS REQUIRED AT THE | | | STAIR ON THE FIRST FLOOR, SEE 905.2.2 | | | F.B.C.. | | | | | | 8} THE MASTER BEDROOM AND BEDROOMS #3&4 | | | NEED RECEPTACLES FOR SPACING | | | REQUIREMENTS OF 210.52(A)(1&2). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|