Plan Review Notes
Plan Review Notes For Permit 04100136
Permit Number 04100136
Review Stop E
Sequence Number 2
Notes
Date Text
2004-11-18 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE RISER DIAGRAM SHOWS THE 100AMP
 PANEL FEEDING THE PANEL MARKED 250, THE
 PANEL SCHEDULE INDICATES THIS AS 200
 AMPS, AND NO FEED FROM EITHER PANEL TO
 THE OTHER IS SHOWN.
  
 2} BOTH PANELS ARE BOTTOM FED, PLEASE
 CLARIFY, SEE RISER.
  
 3} SHOW CONDUCTOR SIZE, CONDUIT SIZE AND
 OCP FOR THE FEED BETWEEN PANELS.
  
 4} PLEASE DRAW THE LOCATION OF THE MAIN
 DISCONNECT ON THE PLAN.
  
 5} THERE IS ONLY ONE SMALL APPLIANCE
 CIRCUIT ON THE SCHEDULE, THE CALC LISTS
 3, PLEASE CORRELATE.
  
 6} THE BATH CIRCUITS LISTED ON THE
 SCHEDULE@15 AMPS DO NOT COMPLY WITH
 210.11(C)(3),20AMP.
  
 7} A SMOKE DETECTOR IS REQUIRED AT THE
 STAIR ON THE FIRST FLOOR, SEE 905.2.2
 F.B.C..
  
 8} THE MASTER BEDROOM AND BEDROOMS #3&4
 NEED RECEPTACLES FOR SPACING
 REQUIREMENTS OF 210.52(A)(1&2).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved