Plan Review Notes
Plan Review Notes For Permit 04100136
Permit Number 04100136
Review Stop B
Sequence Number 2
Notes
Date Text
2004-11-30 00:00:00CHECKLIST:
 1-PROVIDE ENERGY CALCULATIONS AS REQ'D
 BY SEC. 103 CHAPTER 13 FBC 2001.
  
 2-PROVIDE SOIL TEST REPORT.
  
 3-SPECIFY SIZE OF ATTIC ACCESS ABOVE
 MASTER BEDROOM WARDROBE. SEC. 2309.6
 FBC
  
 4-FLOOR PLANS ARE MISSING A LOT OF
 DIMENSIONS. ALSO, SOME DIMENSIONS ARE
 OVERLAPPING WITH OTHER INFORMATION AND
 ARE NOT LEGIBLE.
 **THERE ARE NOT DIMENSIONS FOR MASONRY
 OPENINGS AND FOR LOCATION OF CONCRETE
 BLOCK REINFORCING COLUMNS. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 5-SPECIFY SAFETY GLASS WHERE REQUIRED
 BY
 SEC. 2405.2.1 FBC 2001. SEE PLANS.
  
 6-REVISE STAIR WINDERS TO COMPLY WITH
 SECTION 1007.8.1 FBC 2001.
  
 7-SPECIFY FIREBLOCKING AT STAIRS AS
 REQUIRED BY SEC. 2305.1.4 FBC 2001.
  
 8-ONLY 2 SETS OF DRAWINGS ARE REQUIRED.
  
 9-PROVIDE COMPLETE DETAILS/SPECS FOR
 CEILING INSTALLATION AT FRONT AND BACK
 PORCHES. SEC. 2504.2 FBC 2001 AND ASTM
 C926 AND ASTM C1063.
  
 10-UPDATE TRUSS ANCHOR SCHEDULE. USE
 LATEST USP OR SIMPSON CATALOGUE.
 PROVIDE
 COMPLETE ENGINEERING CALCULATIONS FOR
 TYPE AND NUMBER OF FASTENERS THAT ARE
 DIFFERENT FROM THOSE PUBLISHED BY THE
 MANUFACTURER. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 CLARIFY WHY ARE THERE ADDITIONAL
 FASTENERS SPECIFIED ON RIGHT HAND SIDE
 COLUMN OF TRUSS SCHEDULE.
  
 11-PROVIDE COMPLETE FLORIDA OR LOCAL
 PRODUCT APPROVAL (2 COPIES) FOR:
 A) SINGLE HUNG WINDOWS.
 B) FIXED WINDOWS WITH SIZES AND SHAPES
 AS SHOWN ON PLANS.
 C) ROOF TILE.
 D) GLASS BLOCK.
 E) STRUCTURAL CONNECTORS (USP/SIMPSON).
 F) HORIZONTAL SLIDING WINDOWS.
 G) MECHANICAL ROOM EXTERIOR DOOR.
 H) FRENCH DOORS.
 I) ENTRY DOOR.
  
 12-ENGINEER TO PROVIDE COMPLETE SPECS
 FOR ROOF ASSEMBLY, INCLUDING TILE
 FASTENING AS REQUIRED BY SEC. 104.2.1.1
 CITY AMENDMENTS TO FBC 2001.
  
 13-PROVIDE COMPLETE INFORMATION FOR
 STORM SHUTTERS INCLUDING: KEY PLAN AND
 COMPLETE INSTALLATION SCHEDULE (SEE
 SAMPLE).
 ALSO, CLEARLY MARK ON DRAWINGS SPECIFIC
 MOUNTING CONDITIONS AND ANCHOR TYPE AND
 SPACING TO BE USED ACCORDING TO THE
 DESIGN PRESSURES, EDGE DISTANCE, PANEL
 SPAN, CONNECTION TYPE AND STRUCTURE TO
 BE ATTACHED TO (MASONRY OR CONCRETE).
  
 14-AFTER CORRECTIONS ARE DONE, PLEASE
 TAKE DRAWINGS TO THE HISTORIC DISTRICT
 FOR APPROVAL STAMPS PRIOR TO SUBMITTAL
 TO THE BUILDING DEPARTMENT TO EXPEDITE
 THE REVIEW PROCESS.
  
 15-RE-SUBMITTAL FEES WILL BE CHARGED AT
 TIME OF RE-SUBMITTAL. SEE ENCLOSED FEE
 SCHEDULE.
  
 16-DETAIL K ON SHEET A-11 IS MISSING
 INFORMATION. SEE PLANS.
  
 17-PROVIDE ONLY DETAILS/SECTIONS THAT
 APPLY TO THIS PROJECT TO EXPEDITE REVIEW
 PROCESS AND AVOID CONFUSSIONS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.
  