2004-10-22 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
 FBC-2001 BUILDING
  
 1) SHT A-9 SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN, NOR DOES IT
 MEET CODE REQUIREMENTS.
 A) FIXTURES FROM DIFFERENT BATHROOMS
 AND DIFFERENT LAYOUTS, (DIFFERENT WALL),
 ARE SHOWN ON THE SAME COMMON WALL.
 B) WASH MACHINE CONNECTION NOT SHOWN.
 C) ONLY TWO W/C'S SHOWN ON RISER DIAGR-
 AM FIRST FLOOR, WHEN THREE ARE SHOWN ON
 THE FLOOR PLAN.
 D) FIRST FIXTURES ON RISER DIAGRAM ARE
 NOT LABELED. IF THOSE FIXTURES ARE THE
 KITCHEN SINK, THEY SHOULD BE CONNECTED
 TO THE BLDG. DRAIN UPSTREAM OF THE POW-
 DER ROOM.
 E) GARAGE SINK NOT SHOWN ON RISER DIAG-
 RAM.
 F) BOTH BATHROOMS ON THE FIRST FLOOR
 SHOW TWO LAVS ON THE RISER DIAGRAM, WHEN
 BATH #2 ONLY HAS ONE ON THE FLOOR PLAN.
 G) MASTER BATH SHOWER NOT SHOWN ON THE
 RISER DIAGRAM.
 H) LAV IN UPSTAIRS BATHROOM #3 IS SHOWN
 GOING OUTSIDE OF THE BLDG. AND NOT IN
 THE ROOM.
 I) SIZE ALL PIPES IN SANT. RISER DIAGR-
 AM.
 SECTION 104.2.1
 2) MAY I SUGGEST THAT YOU HAVE YOUR
 PLUMBING CONTRACTOR INDICATE HOW THE
 PLUMBING WILL BE INSTALLED AND DRAW THE
 SANITARY RISER DIAGRAM, AND THEN REDRAW
 THE RISER ON THE PLANS.
  