| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING |
| | INSTALLED. MAINS/BRKRS AND PANELS ARE |
| | ALL TO BE RATED FOR THE AVAILABLE FAULT |
| | CURRENT PER 110.9. |
| | |
| | 2} THE GEC SYSTEM MUST COMPLY WITH ALL |
| | AVAILABLE. SEE 250.52(A)(3), FOOTER |
| | STEEL. |
| | |
| | 3} THE RISER SHOWS 2 ELECTRIC PANELS |
| | BUT THERE ARE THREE ON THE DRAWING. |
| | PLEASE |
| | INCLUDE ALL PANELS ON THE RISER. |
| | |
| | 4} PLEASE PROVIDE A PANEL SCHEDULE SO |
| | THAT BRANCH CIRCUIT COMPLIANCE MAY BE |
| | DETERMINED. |
| | |
| | 5} PLEASE NOTE THE CALCULATION FOR SMALL |
| | APPLIANCE CIRCUITS MUST COMPLY WITH |
| | 210-16(A). 1500VA EACH. |
| | |
| | 6} RECEPTACLES IN THE GARAGE MUST COMPLY |
| | WITH 210.8(A)(2), GFI. |
| | |
| | 7} SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS.SEE REVIEWED SET OF PLANS FOR |
| | LOCATIONS IN QUESTION.NFPA-72 |
| | 8-1.4.1.6.2 AND 905.2.2 FBC. |
| | |
| | 8} THE RECEPTACLE IN BATH #4 MUST BE GFI |
| | PER 201.8(A)(1). |
| | |
| | 9} PLEASE SEE MISSING RECEPT REQUIRED |
| | FOR A/C EQUIPMENT 210.63. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |