Plan Review Notes
Plan Review Notes For Permit 04100136
Permit Number 04100136
Review Stop E
Sequence Number 1
Notes
Date Text
2004-10-14 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALLED. MAINS/BRKRS AND PANELS ARE
 ALL TO BE RATED FOR THE AVAILABLE FAULT
 CURRENT PER 110.9.
  
 2} THE GEC SYSTEM MUST COMPLY WITH ALL
 AVAILABLE. SEE 250.52(A)(3), FOOTER
 STEEL.
  
 3} THE RISER SHOWS 2 ELECTRIC PANELS
 BUT THERE ARE THREE ON THE DRAWING.
 PLEASE
 INCLUDE ALL PANELS ON THE RISER.
  
 4} PLEASE PROVIDE A PANEL SCHEDULE SO
 THAT BRANCH CIRCUIT COMPLIANCE MAY BE
 DETERMINED.
  
 5} PLEASE NOTE THE CALCULATION FOR SMALL
 APPLIANCE CIRCUITS MUST COMPLY WITH
 210-16(A). 1500VA EACH.
  
 6} RECEPTACLES IN THE GARAGE MUST COMPLY
 WITH 210.8(A)(2), GFI.
  
 7} SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.SEE REVIEWED SET OF PLANS FOR
 LOCATIONS IN QUESTION.NFPA-72
 8-1.4.1.6.2 AND 905.2.2 FBC.
  
 8} THE RECEPTACLE IN BATH #4 MUST BE GFI
 PER 201.8(A)(1).
  
 9} PLEASE SEE MISSING RECEPT REQUIRED
 FOR A/C EQUIPMENT 210.63.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  