Plan Review Notes
Plan Review Notes For Permit 04100134
Permit Number 04100134
Review Stop M
Sequence Number 1
Notes
Date Text
2004-10-15 00:00:00PROVISO:
 TRANSFER GRILLES INDICATED ABOVE THE
 DOORS ARE NOT SIZED.MINIMUM OF 50 SQ
 INCHES OF FREE AREA REQUIRED PER 100 CFM
 OF SUPPLY AIR.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved