2004-10-19 00:00:00DENIED:
 1.PLEASE NOTE ALL ENGINEERED PLANS ARE
 TO BE SIGNED, SEALED AND DATED PER FS
 471.025 FAC 61G15-23.
  
 2.LETTER INDICATES ROOF TOP CHANGE
 OUT WHICH CONFLICTS WITH WORK DESCRIBED
 ON THE PERMIT APPLICATION.
  
 3.IS THE NEW DUCT WORK INDICATED ON
 THE PERMIT APPLICATION IS FOR THE
 RECEIVING OFFICE AREA SHOWN ON THE
 PLANS SUBMITTED.WILL THIS BE A CHANGE
 OUT OF DUCT OR IS THE ENTIRE SYSTEM
 INCLUDING THE UNIT NEW?PLEASE CLARIFY.
  
 4.PLANS INDICATE ROOF CURBS TO BE A
 MINIMUM OF 14".PLEASE NOTE, PER 2001
 FBC 1511.7, CURBS SHALL BE A MINIMUM OF
 8" FROM THE ROOF SURFACE.
  