| Plan Review Notes For Permit 04100118 |
| Permit Number |
04100118 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-10-19 00:00:00 | DENIED: | | | 1.PLEASE NOTE ALL ENGINEERED PLANS ARE | | | TO BE SIGNED, SEALED AND DATED PER FS | | | 471.025 FAC 61G15-23. | | | | | | 2.LETTER INDICATES ROOF TOP CHANGE | | | OUT WHICH CONFLICTS WITH WORK DESCRIBED | | | ON THE PERMIT APPLICATION. | | | | | | 3.IS THE NEW DUCT WORK INDICATED ON | | | THE PERMIT APPLICATION IS FOR THE | | | RECEIVING OFFICE AREA SHOWN ON THE | | | PLANS SUBMITTED.WILL THIS BE A CHANGE | | | OUT OF DUCT OR IS THE ENTIRE SYSTEM | | | INCLUDING THE UNIT NEW?PLEASE CLARIFY. | | | | | | 4.PLANS INDICATE ROOF CURBS TO BE A | | | MINIMUM OF 14".PLEASE NOTE, PER 2001 | | | FBC 1511.7, CURBS SHALL BE A MINIMUM OF | | | 8" FROM THE ROOF SURFACE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|