Plan Review Notes For Permit 04100017
Permit Number 04100017
Review Stop B
Sequence Number 2
Notes
Date Text
2005-06-24 00:00:00DENIED
  
 1.PERMIT APPLICATION HAS EXPIRED.
 OVER 180 DAYS WITH NO ACTIVITY.FBC
 104.5.1.3.CONTACT NEIL MELICK BUILDING
 OFFICIAL TO HAVE PERMIT APPLICATION
 REINSTATED. 561-805-6654
  
 2. 713.13(2) F.S.THE NOTICE OF
 COMMENCEMENT MUST BE RE-RECORDED BECAUSE
 THE DESCRIBED IMPROVEMENT OR
 CONSTRUCTION DID NOT COMMENCE WITHIN 90
 DAYS OF RECORDING.
  
 3.THE BOTTOM FOOTING SHALL EXTEND NO
 LESS THAN 12" BELOW GRADE.FBC1804.1.3
  
 4.SUBMIT TWO COPIES OF TABLE 600
 ENERGY CALCS.
  
 5.SHOW LEDGER FASTENING SPACING FOR
 ROOF AND FLOORS.
  
 6.MINIMUM ROOF SHEATHING THICKNESS IS
 5/8" FBC 2309.3.1
  
 7.SHOW A ROOF SHEATHING NAILING
 SCHEDULE COMPLYING WITH FBC2306.1 WPB
 AMMENDMENTS.
  
 8.SUBMIT 2 COPIES OF PRODUCT APPROVALS
 WITH QUALITY ASSURANCE FOR ROOFING,
 WINDOWS, IMPACT PROTECTION AND STRAPS
 AND TIE DOWNS.
 **ALL PRODUCT APPROVALS SUBMITTED SHALL
 HAVE THE FOLLOWING STATE APPROVALS
 ATTACHED**
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 9.SHOW A WALL FRAMING DETAIL AND
 INCLUDE STRAPING AND TIE-DOWNS, HEADERS
 AND SIZE.ALSO SHOW TIE-IN TO
 FOUNDATION.
  
 10.SUBMIT FLOORING PLANS AND ROOF
 PLANS SEPERATLY.INCLUDE ALL TIE-INS
 USED FROM FOOTINGS UP INCLUDING ROOF
 FRAMING. THIS IS NEEDED FOR STEAMROOM
 AND FRONT PORCH.
  
 11.NEW ROOF OVER STEAM ROOM APPEARS TO
 BE FLOATING WITH OUT MUCH SUPPORT.
 REDESIGN THIS ROOF AND INCLUDE DETAILS
 FOR ALL CONNECTIONS AND METHOD OF TIE-IN
 AND TIE-DOWN.
  
 12.SHOW WHAT METHOD WILL BE USED FOR
 ROOF VENTILATION.
  
 13. ON FRONT PORCH THE BEAM SUPPORTING
 JOISTS HAS NO MID SPAN SUPPORT.
 INCREASE BEAM SIZE OR ADD AN ADDITIONAL
 FOOTING.
  
 14.SUBMIT A NEW BATHROOM PLAN.
 EXISTING BATHROOM IS 96" ON NEW PLAN
 BATHROOM IS OVER 20FT LONG.
 NEW PLAN ONLY SHOWS ON WALL. SHOW FLOOR
 PLAN.
  
 15.SHOW HOW BEAM WILL BE TIED INTO
 EXISTING DECK.
  
 16.SHOW STAIR DETAIL. FBC 1007.3
  
 17.VERIFY FOOTING SIZE ON ROOM
 ADDITION.IT APPEARS TO BE UNDERSIZED.
 FBC1804
  
 18.NOTE PLANS HAVE INSUFFICIENT
 INFORMATION FOR A COMPLETE REVIEW.
 AFTER REVIEWING RESUBMITTED PLANS
 ADDITIONAL CORRECTIONS MAY ARISE.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER