Plan Review Notes
Plan Review Notes For Permit 04100003
Permit Number 04100003
Review Stop E
Sequence Number 1
Notes
Date Text
2004-10-08 00:00:00**************** UNSAT ************
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH A PANEL SCHED-
 -ULE TO BE SUBMITTED. PANEL SCHEDULE TO
 SHOW ALL MIN CIRCUITS PER 2002 NEC.
 AWG/OCP. 215.5
  
 2)NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
 3)NOTE: INFORMATION USE: PLEASE SEE
 RECEPT SHOWN IN "REAR MASTER CLOSET"
 MAY NOT BE USED FOR "PLUG-IN" TRANSFORM-
 -ERS. THIS IS ONLY A NOTE DUE TO
 COMBUSTIBLES IN CLOSETS.
  
 4)NOTE: PLEASE SEE 210.52 FOR POSSIBLE
 FIXED GLASS PANELS? ARE ALL GLASS PANELS
 /DOORS SHOWN MOVEABLE? IF NOT RECEPTS
 WILL BE REQUIRED PER 210.52
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]