| Plan Review Notes For Permit 04100003 |
| Permit Number |
04100003 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-10-08 00:00:00 | **************** UNSAT ************ | | | | | | 1)NOTE: PLEASE SHOW ALL CIRCUITING ON | | | PLANS AND CORRELATE WITH A PANEL SCHED- | | | -ULE TO BE SUBMITTED. PANEL SCHEDULE TO | | | SHOW ALL MIN CIRCUITS PER 2002 NEC. | | | AWG/OCP. 215.5 | | | | | | 2)NOTE: PLEASE LIST ALL THE REQ'D | | | DEDICATED BATH(S) CIRCUIT(S) ON PANEL | | | SCHEDULE. PER 210.52D, 210.11C3 | | | | | | 3)NOTE: INFORMATION USE: PLEASE SEE | | | RECEPT SHOWN IN "REAR MASTER CLOSET" | | | MAY NOT BE USED FOR "PLUG-IN" TRANSFORM- | | | -ERS. THIS IS ONLY A NOTE DUE TO | | | COMBUSTIBLES IN CLOSETS. | | | | | | 4)NOTE: PLEASE SEE 210.52 FOR POSSIBLE | | | FIXED GLASS PANELS? ARE ALL GLASS PANELS | | | /DOORS SHOWN MOVEABLE? IF NOT RECEPTS | | | WILL BE REQUIRED PER 210.52 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|