| 2004-11-18 00:00:00 | ************ UNSAT 2ND REVIEW ********* |
| | |
| | PLEASE SEE SOME COMMENTS FROM PREVIOUS |
| | REVIEW STILL NEED TO BE ADDRESSED. |
| | |
| | |
| | 1)NOTE: PLEASE SEE 210.52D FOR RECEPT |
| | SPACING IN BATHRMS. ALL GFI'S ARE TO BE |
| | WITHIN 3' OF SINK EDGE. |
| | PLEASE SEE PREVIOUS NOTE# 5 |
| | |
| | 2)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS. PLEASE SEE KITCHEN GFI AND SD'S |
| | AND ANY OTHER POSSIBLE DEVICES. |
| | |
| | *** NEW COMMENTS DUE TO CHANGES IN PLANS |
| | AND COMPLETE SUBMITTAL. *** |
| | |
| | |
| | |
| | |
| | 1) NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 2)NOTE: PLEASE SEE LOAD CALCULATIONS |
| | WHICH SHOWS 20KW OF HEAT FOR A/C ON EACH |
| | PANEL, YET PANEL SCHEDULE SHOWS 2-2POLE |
| | 30'S ? PLEASE ALSO SEE MECH PLANS WHICH |
| | SHOWS A DIFFERENT LOAD FOR A/C UNIT |
| | HEAT. |
| | PLEASE ALSO SEE CIRCUITING ON PLANS FOR |
| | A/C AHU'S ALSO. |
| | ALL OF THESE NEED TO CORRELATE. |
| | |
| | 3)NOTE: PLEASE SEE 220.31B FOR LOAD |
| | CALCULATIONS. PLEASE ADJUST. |
| | |
| | 4)NOTE: PLEASE SEE MAINS ARE SHOWN AS |
| | 3-POLE BRKR DISC'S, HOWEVER SERVICE IS |
| | SHOWN AS SINGLE PHASE?? |
| | PLEASE CORRELATE. |
| | |
| | 5)NOTE: PLEASE SEE 210.52B1, |
| | 220.16,210.11C1 FOR CIRCUITING OF DINING |
| | RM RECEPTS. |
| | |
| | 6)NOTE: PLEASE SHOW A DEVICE/FIXTURE |
| | LEGEND. ANY RECESSED FIXTURES SHOULD BE |
| | SHOWN WITH MAX WATTAGE. 220.3B4 |
| | |
| | 7)NOTE: PLEASE SEE ATTACHED COPY OF FS |
| | 553.80(2)(B) WITH RESPECT TO DESIGN |
| | PROFESSIONAL FOR REPEATED COMMENTS. |
| | THIS IS ONLY A NOTICE GIVEN AT THIS |
| | TIME. |
| | |
| | PLEASE SEE ANY COMMENTS FROM ANY OTHER |
| | REVIEWERS WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | PLEASE REMOVE ALL OLD SHEETS AND INSERT |
| | NEW SHEETS INTO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |