2004-10-25 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHOW THE LOCATION OF THE WASH MACHINE
 CONNECTION REQUIRED BY TABLE 403.1
 2) SHT P-3 SANITARY RISER #4, ONLY THE
 FIXTURES WITHIN THE BATHROOM GROUP SHALL
 CONNECT TO THE WET-VENTED HORIZONTAL
 BRANCH DRAIN. THE BAR SINK IN THE ENTRY
 SHALL DISCHARGE DOWNSTREAM OF THE WET
 VENT. SECTION 909.1
 3) ALL SHEETS, THE DATE THE ARCHITECT
 SIGNS AND SEALS THE PLANS SHALL BE ON
 THE SEAL. FAC 6161-16.003 & FAC 61G1-16.
 004(5). FS 481.2055
  