2004-10-26 00:00:00DENIED:
 1.PLAN SHEET M-2 HVAC GENERAL NOTES
 #2, "INSTALLATION OF SUPPLY/RETURN AIR
 PLENUM SLOTS LOCATED IN THE CROWN
 MOLDINGS".PLAN SHEET M-1 DOES NOT
 INDICATE ANY RETURN AIR GRILLES.PER
 2001 FBC(M) 601.4, RETURN AIR REQUIRED
 FROM ALL HABITABLE AREAS ISOLATED FROM
 THE RETURN AIR.
  
 2.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.