| Notes |
| Date |
Text |
| 2004-10-26 00:00:00 | DENIED: | | | 1.PLAN SHEET M-2 HVAC GENERAL NOTES | | | #2, "INSTALLATION OF SUPPLY/RETURN AIR | | | PLENUM SLOTS LOCATED IN THE CROWN | | | MOLDINGS".PLAN SHEET M-1 DOES NOT | | | INDICATE ANY RETURN AIR GRILLES.PER | | | 2001 FBC(M) 601.4, RETURN AIR REQUIRED | | | FROM ALL HABITABLE AREAS ISOLATED FROM | | | THE RETURN AIR. | | | | | | 2.AUXILIARY DRAIN PAN WITH OVERFLOW | | | PROTECTION REQUIRED PER 2001 FBC(M) | | | 307.2.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|