| 2004-10-06 00:00:00 | ************* UNSAT ***************** |
| | |
| | 1)NOTE: PLEASE SEE THERE ARE TWO SHEET |
| | E-1 AND E-2 IN EACH SET WITH ALL FOUR |
| | SHEETS SHOWING THE SAME THING? |
| | PLEASE SUBMIT TWO COMPLETE SETS FOR |
| | REVIEW AND STAMPING. |
| | |
| | 2)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH PANEL SCHEDULE |
| | (S) TO BE SUBMITTED SHOWING ALL MIN |
| | CIRCUITS ETC TO MEET 2002 NEC. |
| | PLEASE SHOW SIZE OF EXISTING PANELS/ |
| | SERVICE. |
| | SUBMIT LOAD CALCULATTIONS. |
| | 215.5,220.31B |
| | |
| | 3)NOTE: PLEASE SEE 210.70 AND LS101 5-8 |
| | FOR REQUIRED EGRESS LIGHTING FIXTURES. |
| | PLEASE CORRELATE ELECTRICAL PLANS WITH |
| | MECHANICAL PLANS. M-SHEETS SHOWS A FAN/ |
| | LT UNIT, YET THIS IS NOT SHOWN ON E-PLAN |
| | 'S. ELECTRICAL PLANS ONLY SHOW A J-BOX. |
| | PLEASE SHOW ON ELECTRICAL PLANS IF IN |
| | DESIGN. |
| | |
| | 4) NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210.8A-6 |
| | |
| | 5) NOTE: PLEASE LIST ALL THE REQ'D |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | PLEASE ALSO SEE RECEPTS REQUIRED TO BE |
| | W/IN 3'OF LAV/SINK. |
| | PLEASE ALSO SEE IT IS NOT PERMITTED TO |
| | CROSS OVER A SINK TO PLUG INTO A RECEPT. |
| | GFI TO BE MOVED TO CENTER OF TWO SINKS |
| | OR ADD AN ADDITIONAL RECEPT. |
| | |
| | 6)NOTE: PLEASE SEE FBC CHAPTER 34 |
| | 3404.7.2.6 |
| | |
| | 7)NOTE: PLEASE SEE 408.7,240.24D, PANEL |
| | NOT PERMITTED IN CLOTHES CLOSET. |
| | |
| | 8)NOTE: PLEASE SEE 210.52 FOR MISSING |
| | RECEPT ON 2' OF WALL SPACE. BEDRM #1 |
| | |
| | PLEASE SEE POSSIBLE COMMENTS FROM OTHER |
| | REVIEWERS WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW SHEETS INTO TWO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |