| 2005-02-03 00:00:00 | | | | THE LOAD CALCULATIONS SUBMITTED MUST BE | | | CORRECTED AS FOLLOWS. | | | | | | 1} THE PLANS MUST CONTAIN THE PRINTED AN | | | SIGNED NAME OF THE DESIGNER OF RECORD | | | PER 104.2.1 FBC. | | | | | | 2} THE GENERAL LIGHTING LOAD IS LISTED @ | | | 6600 AND THEN A CALULATION OF 3 WATTS | | | PER SQUARE FOOT IS SHOWN, WHICH WOULD BE | | | THE GENERAL LIGHTING LOAD, @ 3000. | | | PLEASE CORRELATE. | | | | | | 3} THE SMALL APPLIANCE LOAD MUST COMPLY | | | WITH 220.16, 2@ 1500=3000WATTS MINIMUM. | | | | | | 4} THE WASHER IS INCORRECTLY CALCULATED | | | AT 10000 WATTS, BUT MUST BE A MINIMUM OF | | | 1500 WATTS IF REFERRING TO THE LAUNDRY | | | LOAD REQUIREMENT. | | | | | | 5} A/C #1&2 ARE SHOWN AS 5000 EACH, AND | | | SHOWN AGAIN AT 15000 AND 10000. PLEASE | | | CORRELATE. | | | | | | 6} THE RANGE MUST BE CALCULATED PER | | | 220.19. | | | | | | 7} CLARIFY "HWIT" ON CALC. | | | | | | 8} THE POOL PUMP AND HEATER MUST BE | | | CALCULATED AT 125%. SEE ARTICLES 424 & | | | 430. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|