| Date |
Text |
| 2004-10-22 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04090836 |
| | ADD: 1400 CENTREPARK DR # 10TH FL |
| | CONT: PASS INTERNATIONAL |
| | TEL: (561)239-0125 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1STREVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE THE SUITE NUMBER WHERE WORK |
| | WILL BE COMPLETED UNDER THIS PERMIT. |
| | |
| | 2) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 3) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE |
| | STOP PARTITIONS, HORIZONTAL EXIT PART- |
| | ITIONS, EXIT ENCLOSURES, AND FIRE |
| | RATED WALLS REQUIRED TO HAVE PROTECTED |
| | OPENINGS SHALL BE EFFECTIVELY AND |
| | PERMANETLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE |
| | AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| | TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| | CEILING CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| | PROTECT ALL OPENINGS". |
| | |
| | 4) PLANS INDICATE IN THE LEGOND SHEET 1, |
| | 1 HR WALL AT STAIRWELL, TABLE 705.2.1. |
| | REQUIRES A 2HR WALL AT STAIRWAYS ( SHAFT |
| | CONSTRUCTION OVER 4 STORIES). |
| | |
| | 5) PLANS DO NOT INDICATE THAT THIS BUILD |
| | ING IS FIRE SPRINKLERED,DOOR 1 AND 12 |
| | DO NOT MEET THE REQUIREMENTS OF: |
| | 1004.1.4 WHERE 2 OR MORE EXITS OR |
| | EXIT ACCESS DOORS ARE REQUIED, AT LEAST |
| | 2 OF THE EXIT OR EXIT ACCESS DOORS SHALL |
| | BE PLACED A DISTANCE APART EQUAL TO NOT |
| | LESS THAN 1/2 OF THE LENGTH OF THE MAX- |
| | IMUM OVERALL DIAGONAL DIMENSION OF THE |
| | BUILDING OR AREA TO BE SERVED. |
| | |
| | 6) SHEET 2 DETAIL 2 PROVIDE THE RATED |
| | WALL ASSEMBLY NUMBER FOR 1 HR RATING, |
| | EITHER UL, GYPSUM, ETC... |
| | |
| | 7)DOOR SCHEDULE, DOOR# 1/12 ARE EXISTING |
| | RATED DOORS, BUT NOT NOTATION AS TO |
| | DOOR CLOSURE. 705.1.3.5 FIRE DOORS SHALL |
| | BE EQUIPPED WITH AN APPROVED CLOER. |
| | |
| | 8) TABLE 803.3 MINIMUM INTERIOR FINISH |
| | CLASSIFICATION; PROVIDE INFORMATION |
| | BASED ON INTERIOR FINISH REQUIREMENTS |
| | BASED ON OCCUPANCY |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | JIM WITMER |
| | BUILDING PLAN REVIEW |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |