| Plan Review Notes For Permit 04090827 |
| Permit Number |
04090827 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-10-07 00:00:00 | ************DENIED********************** | | | | | | 1) NEW FIRE ALARM SYSTEMS SHALL BE UL | | | AND LISTED FOR CENTRAL STATION SERVICE. | | | | | | 2) ALL NEW FIRE ALARM SYSTEMS THAT | | | SUPERVISE FIRE SPRINKLER SYSTEMS SHALL | | | BE UL CERTIFICATED AND HAVE DOCUMENT | | | ATTESTING TO THIS CERTIFICATION PRIOR TO | | | FINAL OF APPROVAL OF THE FIRE ALARM | | | SYSTEM. | | | | | | 3) THE FIRE ALARM SYSTEM SHALL BE | | | CLASS "A" OR FULLY ADDRESSABLE. | | | | | | 4) THE WEST PALM BEACH FIRE MARSHAL | | | REQUIRES DUCT DETECTORS TO ACTIVATE A | | | GENERAL FIRE ALARM NOT A SUPERVISORY. | | | | | | NATE MCCRAY, CAPTAIN | | | 561-835-2910 OR 561-805-6722 |
|