| Plan Review Notes For Permit 04090795 |
| Permit Number |
04090795 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-03-14 00:00:00 | PROVISO: | | | MECHANICAL PLANS ARE CODE COMPLIANT & | | | APPROVED. | | | | | | SUBMITTAL FOR THE VENTLESS FIRE PLACE IS | | | STILL UNDER SCRUTINY.PER THE | | | MANUFACTURER'S SPECIFICATIONS, WHEN THE | | | APPLIANCE IS INSTALLATED IN BUILDINGS | | | CONSIDERED "UNUSUALLY TIGHT | | | CONSTRUCTION" ADDITIONAL FRESH AIR MUST | | | BE PROVIDED.PLANS DO NOT HAVE ANY | | | CALCUALTIONS FOR COMBUSTION AIR, WHETHER | | | IT WILL BE REQUIRED OR NOT.PLANS DO | | | NOT INDICATE WHICH MODEL IS TO BE | | | INSTALLED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|