2004-10-21 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT M-2 SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN, NOR DOES IT
 MEET CODE REQUIREMENTS.
 A) W/C IN THE POWDER ROOM IS NOT VENTED
 SECTION 901.2.1
 B) CABANA BATH SHOWN ON THE FLOOR PLAN
 IS NOT SHOWN ON THE RISER DIAGRAM. SECT-
 ION 104.2.1
 C) WASH MACHINE REQUIRES A TRAP AND A
 STANDPIPE. ALSO A CLEANOUT IS REQUIRED
 ON THE WASH MACHINE STACK MINIMUM 4'
 ABOVE THE FLOOR. SECTIONS 1002.1, 802.4,
 AND 708.10
 D) SHOW ALL PIPES SIZES ON THE SANT.
 RISER DIAGRAM. SECTION 104.2.1
  