| Plan Review Notes For Permit 04090795 |
| Permit Number |
04090795 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-10-21 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) SHT M-2 SANITARY RISER DIAGRAM DOES | | | NOT REFLECT THE FLOOR PLAN, NOR DOES IT | | | MEET CODE REQUIREMENTS. | | | A) W/C IN THE POWDER ROOM IS NOT VENTED | | | SECTION 901.2.1 | | | B) CABANA BATH SHOWN ON THE FLOOR PLAN | | | IS NOT SHOWN ON THE RISER DIAGRAM. SECT- | | | ION 104.2.1 | | | C) WASH MACHINE REQUIRES A TRAP AND A | | | STANDPIPE. ALSO A CLEANOUT IS REQUIRED | | | ON THE WASH MACHINE STACK MINIMUM 4' | | | ABOVE THE FLOOR. SECTIONS 1002.1, 802.4, | | | AND 708.10 | | | D) SHOW ALL PIPES SIZES ON THE SANT. | | | RISER DIAGRAM. SECTION 104.2.1 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|