| Plan Review Notes For Permit 04090793 |
| Permit Number |
04090793 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-01-19 00:00:00 | DENIED; | | | 1.FOUNTAIN SHOULD BE PERMITED | | | SEPURATLY. | | | 2.SHOW DETAIL OF WATER HEATER. THERMAL | | | EXPANSION CONTROL REQUIRED PER FBC | | | PLUMBING SEC. 607.3. | | | 3.WATER ISOMETRIC, SHOCK ARRESTORS TO BE | | | INSTALLED PER SEC.604.9. NOT NEEDED ON | | | LAVS, SHR. AND TUBS. | | | 4.DETAIL FOR EMPLOYEE BATHROOM AND BREAK | | | SINK SHOULD BE TRANSFURED FROM 8X11 SHT. | | | AND 8X17 SHT.TO NEW PLUMBING PAGE. | | | 5.MODEL BATHROOM AND KITCHEN. SHOW | | | COMPLIANCE TO THE FAIR HOUSING ACT.SHOW | | | CLEAR FLOOR SPACE AND DETAILS FOR | | | REQUIRED BACKING. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 | | | |
|