Plan Review Notes
Plan Review Notes For Permit 04090781
Permit Number 04090781
Review Stop E
Sequence Number 1
Notes
Date Text
2004-10-06 00:00:00************ UNSAT **********
  
 1)NOTE: PLEASE SEE FAC 61G1-16.004 FOR
 ALL REQUIRED INFORMATION ON TITLE BLOCK.
 PLEASE ALSO SEE FS 481.219 FOR REQUIRED
 CERTIFICATE OF AUTHORIZATION #.
 THIS IS REQUIRED FOR ALL TRADES AND ON
 ALL SHEETS WHEATHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 2)NOTE: PLEASE SEE RECEPTS SHOWN AT
 WINDOW LOCATION FOR WHAT APPEARS TO BE
 THE REQUIRED SHOW WINDOW RECEPTS,
 HOWEVER THERE DOES NOT APPEAR ANY
 INDICATION OF CIRCUITING ? #?
 PLEASE SEE 210.62,220.12A
  
 3)NOTE: PLEASE SEE 700.12E FOR CIRCUIT-
 -ING EM/EXT LTS SHOWN ON PLANS.
 THESE ARE NOW SHOWN ON AN INDIVIDUAL
 CIRCUIT. PLEASE SEE SECTION "E" OF 700.
 .12. TO BE ON WITH GEN LT IN AREA.
  
 PLEASE SEE ANY POSSIBLE COMMENTS BY
 OTHER REVIEWERS WHICH MAY HAVE NA AFFECT
 ONELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS FROM
 PLANS AND ONLY INSERT NEW/ REVISED
 SHEETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD SHEETS MAY BE SUBMITTED
 FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]