Date Text
2004-10-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) INDICATE OCCUPANCY OF SPACE. NEW COM-
 MENTS MAY BE REQUIRED DEPENDING ON OCCU-
 PANCY.
 2) SUBMIT ARCHITECTURAL DETAILS FOR THE
 TOILET ROOMS. SHOW COMPLIANCE WITH SECT-
 IONS 11-4.15, 11-4.16, 11-4.18, 11-4.19
 AND 11-4.22 AND ALL SUBSECTIONS.
 3) SHT P-1 SANITARY RISER DIAGRAM, (MIS-
 LABELED WATER RISER DIAGRAM), HAS HAND
 DRAWN CHANGES WHICH ARE NOT ACCEPTABLE.
 BOTH FLOOR DRAINS DRAWN OUT ON FLOOR
 PLAN, BUT ONE ON RISER. CLAIRFY. SECTION
 104.2.1
 4) SHT P-1 WATER RISER DIAGRAM, AIR
 CHAMBERS ARE NOT APPROVED. REMOVE FROM
 RISER DIAGRAM. SECTION 604.9. - FULL
 OPEN VALVES REQUIRED ON THE TOP OF EVERY
 WATER DOWN-FEED PIPE. SECTION 606.1(4).
 5)ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
  