| 2004-11-04 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)THE FOLLOWING IS REQUIRED FOR THE |
| | SHELL; COMPLIANCE REQUIRED BEFORE |
| | ISSUANCE OF TENANT BUILDOUT PERMIT: |
| | |
| | FROM BUILDING PROVISO DATED 3/02/04: |
| | |
| | PROVIDE SIGNED & SEALED WIND LOAD CALCS |
| | FOR THE LIGHT POLES ASCE7-98 PER FBC16 |
| | (UNSEALED COPIES HAD BEEN SUBMITTED). |
| | |
| | GUARDRAIL TO COMPLY WITH FBC1015.3 AND |
| | 1608; SHOP DRAWINGS TO BE SUBMITTED |
| | BEFORE INSTALLATION. |
| | |
| | FROM ROOFING SUBMITTAL DENIED 8/20/04: |
| | |
| | SUBMITTALS/REVISIONS ARE TO BE REVIEWED |
| | BY DESIGNER OF RECORD. |
| | |
| | ORIGINAL SIGNED, SEALED CALCS REQUIRED |
| | FAC61G15-23.002.THE CA NUMBER FOR THE |
| | ENGINEERING FIRM IS TO BE ON THE TITLE |
| | BLOCK. |
| | |
| | 2.)AS PER ANDREW AIKEN'S AGREEMENT |
| | WITH THE BUILDING OFFICIAL, THE |
| | BUILDING |
| | WAS CHARGED FEES BASED ON A SHELL |
| | VALUATION, WITH ADDITIONAL FEES TO BE |
| | CHARGED AT TIME OF TENANT BUILDOUT. |
| | VALUE HAS BEEN ADJUSTED TO $82,613 (SEE |
| | ATTACHED).ADDITIONAL FEES DUE. |
| | |
| | 3.)SALES COUNTER TO COMPLY WITH |
| | FBC11-7.2; PROVIDE A DETAIL WITH |
| | DIMENSIONS TO SHOW COMPLIANCE. |
| | |
| | |