| Notes |
| Date |
Text |
| 2004-10-05 00:00:00 | ********* UNSAT ************ | | | | | | 1)NOTE: PLEASE CORRELATE RISER DIAGRAM/ | | | LOAD CALCULATIONS AND SPEC SHEET FOR | | | HEAT PUMP AND OCP. | | | | | | SHOWS 2P-25A ON LOAD CALCS, A 2P60A ON | | | SPEC SHEET AND A 2P40A ON PLANS?? | | | PLEASE SEE MIN LOAD ALSO TO BE FIGURED | | | @125% FOR CONTINUOUS LOAD OF 3 OR MORE | | | HOURS. POOL PUMP ALSO. | | | | | | 2)NOTE: PLEASE SEE WIRING DIAGRAM SHOWS | | | A NEW 200A PANEL. PLEASE CLARIFY FEED, | | | #OF CONDUCTORS, CONDUIT ETC | | | 215.5 | | | | | | 3)NOTE: PLEASE SEE LOAD FOR A/C,OCP ETC | | | 424.3B | | | PLEASE SEE 220.31B FOR EXISTING DWELLING | | | -S. A/C AT 100%. | | | PLEASE SEE MISSING SMALL APPLIANCE | | | CIRCUITS PER 220.16, 210.11 ETC | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|