Plan Review Notes
Plan Review Notes For Permit 04090764
Permit Number 04090764
Review Stop B
Sequence Number 7
Notes
Date Text
2007-01-24 17:04:34DENIED BY BUILDING
  
 1)ALL OF THE NEW REVISIONS TO THE PLANS ARE NOT
 CLOUDED AND MARKED WITH THE REVISION NUMBER INSIDE THE
 TRIANGLE.
  
 2) THE TITLE BLOCKS ARE MISSING THE REVISION NUMBERS ON
 SEVERAL SHEETS.
  
 3) THE REVISION DATES IN THE TITLE BLOCK HAVE BEEN
 PARTIALLY CUT OF ON SHEET A6.
  
 4) SPECIFY THE SIZES OF THE ATTIC ACCESS OPENINGS.
  
 5) THE ATTIC ACCESS FROM THE SECOND FLOOR TO AHU-3 DOES
 NOT NEED TO BE SHOWN ON THE FIRST FLOOR PLAN A-2. SHOW
 IT AS A DOOR IN THE WALL OF CLOSET 204 ON THE SECOND
 FLOOR PLAN A-3.
  
 6) WINDOWS (B) IN THE RECONFIGURED 2ND FLOOR SHOWER ARE
 BOTH REQUIRED TO HAVE SAFETY GLAZING OR BE IMPACT
 RESISTANT. THE WINDOW SCHEDULE SHOWS ONLY ONE WITH
 TEMPERED GLASS. PRODUCT APPROVALS SUBMITTED ARE FOR
 LARGE MISSLE IMPACT GLAZING.
  
 7)PLEASE CORRECT THE DOOR AND WINDOW SCHEDULE ON A-9.
 SECOND FLOOR DOORS 71 AND 72 HAVE BEEN OMITTED BUT ARE
 STILL SHOWN ON A-3. CHECK DOORS 15, 16, 46 AND 63 ON
 THE FIRST FLOOR.
  
 8) REVISIONS TO OTHER TRADES AFFECTED BY THESE CHANGES
 WILL BE REQUIRED.
  
 9) THE DIMENSIONS LISTED IN ROOM 128 ARE ILLEGIBLE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714