Plan Review Notes
Plan Review Notes For Permit 04090764
Permit Number 04090764
Review Stop M
Sequence Number 6
Notes
Date Text
2007-01-31 11:32:03MECHANICAL REVISION
 *** DENIED ***
 1) PLEASE SHOW ON ENERGY CALCULATIONS SEER FOR 3 OTHER
 UNITS, LINE 12 C.
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 3) ENERGY CALCULATIONS SHOW TWO GAS WATER HEATERS, LINE
 14 A, AND B, PLEASE SHOW THE LOCATION OF THE GAS WATER
 HEATERS ON THE MECHANICAL PLANS, AND PROVIDE COMBUSTION
 AIR IF REQUIRED.
  
 4) MECHANICAL PLANS PAGE A/C1 SHOW TWO CU4 CONDENSER
 UNITS, PLEASE CORRECT.
  
 5) ARCHITECTURAL FIRM'S ADDRESS AND PHONE NUMBER MUST
 APPEAR IN THE TITLE BLOCK, PER FAC 61G1-16.004.
  
 6) ARCHITECT SEAL IS NOT LEGIBLE, IF SEAL CAN NOT BE
 READ PLANS WILL NOT PASS REVIEW, PLEASE CORRECT.
  
 7) ARCHITECT NEEDS TO DATE HIS SIGNATURE AT THE SEAL,
 PER FAC 61G1-16.004.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.