Plan Review Notes
Plan Review Notes For Permit 04090764
Permit Number 04090764
Review Stop M
Sequence Number 5
Notes
Date Text
2006-12-05 19:06:17-----------------DENIED-----------------
  
 1. REVISED ENERGY CALCULATIONS AND MANUAL J IS
 REQUIRED. SEE PREVIOUS REVIEW NOTE #3 (ATTACHED).
  
 2. AHU#2: PLEASE SHOW 10" FLEX ON SUPPLY GOING TO
 DISTRIBUTION BOX RATHER THAN THE 8X4 GRILL.
  
 3. AHU#2: THERE IS NO RETURN DUCT SHOWN FROM 24X14 R?A
 GRILL TO AHU.
  
 4. AHU#3: DUCT SIZE IS MISSING ON SUPPLY FLEX THAT IS
 FEEDING THE DISTRIBUTION BOX IN THE FOYER/DINING ROOM
 AREA.
  
 5. AHU#5: THE SUPPLY FLEX FEEDING THE DISTRIBUTION BOX
 IN THE FAMILY ROOM IS MARKED AS BOTH 10" AND 12".
 PLEASE CLARIFY BY REMOVING THE INCORRECT SIZE.
  
 6. AHU#5: THE DISTRIBUTION BOX SERVING THE PANTRY AND
 BREAKFAST NOOK IS BEING FED BY A 5" FLEX. PLEASE
 CORRECT.
  
 7. PAGE A/C-1 SHOWS SIX CONDENSERS. THERE ARE ONLY 5
 SYSTEMS. PLEASE CLARIFY.
  
 8. THERE ARE AHUS ON FIRST AND SECOND FLOORS MARKED AS
 AHU#2, WHILE THERE IS NO UNIT MARKED AS AHU#1. PLEASE
 CORRECT.
  
 9. THERE ARE TWO DIFFERENT SYSTEMS ON THE EQUIPMENT
 SCHEDULE MARKED AS SYSTEM #3. PLEASE CORRECT.
  
 10. MECHANICAL NOTE #7 SHOWS 200 CFM FRESH AIR REQUIRED
 ON FIRST FLOOR. HOW IS THIS TO BE PROVIDED. PLEASE
 INDIATE ON THE PLANS.
  
 11. MECHANICAL NOTE #9, THIS REQUIREMENT DOES NOT APPLY
 TO ONE AND TWO FAMILY DWELLINGS. YOU MAY REMOVE THIS
 NOTE OR A FAN SHUT-DOWN TEST WILL BE REQUIRED FOR ALL
 A/C SYSTEMS AT THE FINAL INSPECTION.
  
 12. THE SERVICE PANEL OF ATTIC EQUIPMENT MUST BE
 LOCATED WITHIN SIX FEET OF THE ATTIC ACCESS (SCUTTLE
 HOLE) PER FBC CHAPTER 13, SEC 610.1.ABC.3.5.2
  
 REVIEWED BY:
 RONALD J REGUEIRO
 561.805.6734
 [email protected]