| 2006-12-05 19:06:17 | -----------------DENIED----------------- |
| | |
| | 1. REVISED ENERGY CALCULATIONS AND MANUAL J IS |
| | REQUIRED. SEE PREVIOUS REVIEW NOTE #3 (ATTACHED). |
| | |
| | 2. AHU#2: PLEASE SHOW 10" FLEX ON SUPPLY GOING TO |
| | DISTRIBUTION BOX RATHER THAN THE 8X4 GRILL. |
| | |
| | 3. AHU#2: THERE IS NO RETURN DUCT SHOWN FROM 24X14 R?A |
| | GRILL TO AHU. |
| | |
| | 4. AHU#3: DUCT SIZE IS MISSING ON SUPPLY FLEX THAT IS |
| | FEEDING THE DISTRIBUTION BOX IN THE FOYER/DINING ROOM |
| | AREA. |
| | |
| | 5. AHU#5: THE SUPPLY FLEX FEEDING THE DISTRIBUTION BOX |
| | IN THE FAMILY ROOM IS MARKED AS BOTH 10" AND 12". |
| | PLEASE CLARIFY BY REMOVING THE INCORRECT SIZE. |
| | |
| | 6. AHU#5: THE DISTRIBUTION BOX SERVING THE PANTRY AND |
| | BREAKFAST NOOK IS BEING FED BY A 5" FLEX. PLEASE |
| | CORRECT. |
| | |
| | 7. PAGE A/C-1 SHOWS SIX CONDENSERS. THERE ARE ONLY 5 |
| | SYSTEMS. PLEASE CLARIFY. |
| | |
| | 8. THERE ARE AHUS ON FIRST AND SECOND FLOORS MARKED AS |
| | AHU#2, WHILE THERE IS NO UNIT MARKED AS AHU#1. PLEASE |
| | CORRECT. |
| | |
| | 9. THERE ARE TWO DIFFERENT SYSTEMS ON THE EQUIPMENT |
| | SCHEDULE MARKED AS SYSTEM #3. PLEASE CORRECT. |
| | |
| | 10. MECHANICAL NOTE #7 SHOWS 200 CFM FRESH AIR REQUIRED |
| | ON FIRST FLOOR. HOW IS THIS TO BE PROVIDED. PLEASE |
| | INDIATE ON THE PLANS. |
| | |
| | 11. MECHANICAL NOTE #9, THIS REQUIREMENT DOES NOT APPLY |
| | TO ONE AND TWO FAMILY DWELLINGS. YOU MAY REMOVE THIS |
| | NOTE OR A FAN SHUT-DOWN TEST WILL BE REQUIRED FOR ALL |
| | A/C SYSTEMS AT THE FINAL INSPECTION. |
| | |
| | 12. THE SERVICE PANEL OF ATTIC EQUIPMENT MUST BE |
| | LOCATED WITHIN SIX FEET OF THE ATTIC ACCESS (SCUTTLE |
| | HOLE) PER FBC CHAPTER 13, SEC 610.1.ABC.3.5.2 |
| | |