| 2007-03-12 08:39:31 | |
| | |
| | REVISION DENIED/INCOMPLETE INFORMATION. |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW |
| | |
| | 1} THE PANEL SCHEDULES MUST INCLUDE BRANCH/FEEDER |
| | CIRCUIT CONDUCTOR AND OVER CURRENT PROTECTION SO THAT |
| | COMPLIANCE MAY BE REVIEWED PER 106.3.5.4 FBC AS |
| | AMENDED. SEE PERMITTED SET . |
| | |
| | 2} THE SCHEDULES MARKED "GENERAL, CENTER AND LEFT" IS |
| | UNACCEPTABLE AND CANNOT BE CORRELATED WITH LOCATION OF |
| | THE PANELS ON THE PLAN. INDICATE THE PANEL DESIGNATIONS |
| | AT THE LOCATION AND ON THE SCHEDULE. |
| | |
| | 3} COMPLETE THE SERVICE CALCULATION. INDICATE SERVICE |
| | AMPERAGE. 215.5. |
| | |
| | 4} A WOOD FUELED PIZZA OVEN SHOULD NOT BE IN THE |
| | ELECTRICAL CALCULATIONS. PLEASE REMOVE SAME. |
| | |
| | 5} THE POOL PANEL LOCATION SHOWN ON THE PLAN IS IN |
| | VIOLATION OF 110.26 CLEARANCE REQUIREMENTS. PLEASE |
| | VISIT THE SITE FOR ACTUALLOCATIONS AND ADJUST THE |
| | DRAWING ACCORDINGLY. |
| | |
| | 6} THE CONDENSER DISCONNECTS APPEAR TO BE IN VIOLATION |
| | OF 110.26, PLEASE VERIFY CLEARANCES OF 3' OR MORE. |
| | |
| | 7} THERE IS A LUTRON LIGHTING CONTROL SYSTEM INDICATED |
| | ON THE DRAWING, THIS SYSTEM COST MUST BE ADJUSTED FOR, |
| | AS IT WAS NOT PART OF THE ORIGINAL PLAN. PLEASE |
| | INDICATE THE INCREASED VALUE TO THE PERMIT CLERK AND |
| | OBTAIN A PAID RECEIPT FOR SAME PRIOR TO RESUBMITTING |
| | CORRECTED REVISIONS. 108.3 FBC AS AMENDED. |
| | |
| | 8} THE RISER DIAGRAM INCORRECTLY INDICATES THE CONDUIT |
| | FEEDING THE " HOUSE PANEL ", GOING TO THE TRANSFER |
| | SWITCH. ALSO SHOWS CONDUIT FROM THE " HOUSE PANEL" TO |
| | THE METER/MAIN. INDICATE DESIGNATION FOR THE "HOUSE |
| | PANEL" (SEE NOTE #2). CORRELATE THE RISER DIAGRAM. |
| | |
| | 9} THE GENERATOR EQUIPMENT INDICATED ON THE PLAN MUST |
| | BE PERMITTED SEPARATELY. SUBMIT SPECIFICATIONS AND |
| | PLANS FOR SAME UNDER A RESIDENTIAL GENERATOR |
| | APPLICATION. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | |
| | |