| Plan Review Notes For Permit 04090764 |
| Permit Number |
04090764 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2006-08-11 00:00:00 | *** DENIED *** | | | 1) PLANS ON FILE WERE DONE BY AN ARCTECT | | | (PATRICK SEGRAVES) AND ONLY HE CAN MAKE | | | REVISIONS TO THE MECHANICAL PLANS. | | | | | | 2) PLANS NEED THE JOB ADDRESS ON THEM. | | | | | | 3) MANUAL J CALCULATIONS ON FILE ARE | | | CALLING FOR 73,749 SENSIBLE BTU'S, THE | | | MECHANICAL PLANS ARE CALLING FOR 145,880 | | | SENSIBLE BTU'S, THE PLANS CAN ONLY CALL | | | FOR 20% MORE THAN THE MANUAL J CAL'S, | | | PER 2001 FBC 13-607.1.ABC.1.1, YOU HAVE | | | ABOUGHT 8 TONS TO MUCH. IF YOU ARE | | | PLANING TO KEEP THIS AMOUNT OF COOLING | | | YOU NEED TO SUBMIT NEW ENERGY | | | CALCULATIONS AND MANUAL J CALCULATIONS. | | | | | | 4) SHOW ATTIC ACCESS TO AHU ON PLANS. | | | | | | 5) NEED TO PROVIDE RETURN AIR TO THE | | | LIBRARY. | | | | | | 6) RETURN AIR GRILL 36X16 TO AHU #5 IS | | | TO SMALL FOR A 5 TON SYSTEM PLEASE | | | CORRECT. | | | | | | 7) AHU #1 RETURN AIR DUCT TO 30X18 GRILL | | | IS NOT SIZED. | | | | | | 8) CHECK ALL SUPPLY AIR GRILLS FOR SIZE | | | AND CFM'S SOME ARE MISSING THIS | | | INFORMATION. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. | | | |
|