Plan Review Notes
Plan Review Notes For Permit 04090764
Permit Number 04090764
Review Stop M
Sequence Number 4
Notes
Date Text
2006-08-11 00:00:00*** DENIED ***
 1) PLANS ON FILE WERE DONE BY AN ARCTECT
 (PATRICK SEGRAVES) AND ONLY HE CAN MAKE
 REVISIONS TO THE MECHANICAL PLANS.
  
 2) PLANS NEED THE JOB ADDRESS ON THEM.
  
 3) MANUAL J CALCULATIONS ON FILE ARE
 CALLING FOR 73,749 SENSIBLE BTU'S, THE
 MECHANICAL PLANS ARE CALLING FOR 145,880
 SENSIBLE BTU'S, THE PLANS CAN ONLY CALL
 FOR 20% MORE THAN THE MANUAL J CAL'S,
 PER 2001 FBC 13-607.1.ABC.1.1, YOU HAVE
 ABOUGHT 8 TONS TO MUCH. IF YOU ARE
 PLANING TO KEEP THIS AMOUNT OF COOLING
 YOU NEED TO SUBMIT NEW ENERGY
 CALCULATIONS AND MANUAL J CALCULATIONS.
  
 4) SHOW ATTIC ACCESS TO AHU ON PLANS.
  
 5) NEED TO PROVIDE RETURN AIR TO THE
 LIBRARY.
  
 6) RETURN AIR GRILL 36X16 TO AHU #5 IS
 TO SMALL FOR A 5 TON SYSTEM PLEASE
 CORRECT.
  
 7) AHU #1 RETURN AIR DUCT TO 30X18 GRILL
 IS NOT SIZED.
  
 8) CHECK ALL SUPPLY AIR GRILLS FOR SIZE
 AND CFM'S SOME ARE MISSING THIS
 INFORMATION.
  
 MECHANICAL PLAN REVIEW BY;