Plan Review Notes
Plan Review Notes For Permit 04090764
Permit Number 04090764
Review Stop E
Sequence Number 4
Notes
Date Text
2007-02-15 11:11:28 
  
 REVISION DENIED/INCOMPLETE INFORMATION
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 THE FOLLOWING NEED TO BE ON THE PLAN, ON THE SHEETS
 THAT ARE BEING REVISED. PLEASE KEEP IN MIND THE SHEET
 THAT IS BEING REPLACED WILL BE BASICALLY VOIDED. ALL
 INFORMATION THAT PERTAINS TO THAT SHEET MUST THEREFORE
 APPEAR ON THE REVISED SHEET.
  
 1} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT
 SIZE AND TYPE, GROUNDING DETAILS, LOAD CALCULATIONS,
 PANEL SCHEDULES, SERVICE EQUIPMENT AND PANEL LOCATIONS
 PER 106.3.5.4 FBC. NOTE THERE IS A GENERATOR PANEL NOW
 SHOWN ON THE PLAN, THERE WAS NO GENERATOR APPLICATION
 OR PERMIT FOR THIS RESIDENCE.
  
 2} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 3} PROVIDE PANEL SCHEDULES PER 408.4.
  
 4}PROVIDE LOAD CALCULATIONS PER ARTICLE 220. INDICATE
 WHICH SECTION IS BEING USED.
  
 5} RECEPTACLES ARE REQUIRED TO BE GFI PROTECTED IN THE
 BATHROOMS PER 210.8(A)(1). SOME ARE MISSING THAT
 DESIGNATION ON THE PLAN.
  
 6} RECEPTACLES ARE REQUIRED TO BE GFI PROTECTED FOR THE
 KITCHENCOUNTERTOPS PER 210.8(A)(6)).
  
 7} AT LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT
 EACH ISLAND COUNTER SPACE WITH A LONG DIMENSION OF 600
 MM (24 IN.) OR GREATER AND A SHORT DIMENSION OF 300 MM
 (12 IN.) OR GREATER. 210.52.(C)(2).
  
 8} WET BAR SINKS- WHERE THE RECEPTACLES ARE INSTALLED
 TO SERVE THE COUNTERTOP SURFACES AND ARE LOCATED WITHIN
 1.8 M (6 FT) OF THE OUTSIDE EDGE OF THE WET BAR SINK.,
 GFI PROTECTED 210.8(A)(7).
  
 9}SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
  
 10} THE DISCONNECTS FOR THE CONDENSING UNITS ARE
 MISSING FROM THE PLAN INDICATE LOCATION PER 440.14 AND
 CLEARANCE PER 110.26.
  
 11} THE ARCHITECTS SEAL IS NOT LEGIBLE ON THE PLAN
 481.221 FAC.
  
 12} THERE ARE NO CLOUDS, HIGHLIGHTS OR DELTA 'S ON THE
 PLAN TO INDICATE AREAS IF REVISION. PLEASE INCLUDE SAME
 PER 106.1.3 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  
  
  
  
  
  
  