| | REVISION DENIED/INCOMPLETE INFORMATION |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | THE FOLLOWING NEED TO BE ON THE PLAN, ON THE SHEETS |
| | THAT ARE BEING REVISED. PLEASE KEEP IN MIND THE SHEET |
| | THAT IS BEING REPLACED WILL BE BASICALLY VOIDED. ALL |
| | INFORMATION THAT PERTAINS TO THAT SHEET MUST THEREFORE |
| | APPEAR ON THE REVISED SHEET. |
| | |
| | 1} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT |
| | SIZE AND TYPE, GROUNDING DETAILS, LOAD CALCULATIONS, |
| | PANEL SCHEDULES, SERVICE EQUIPMENT AND PANEL LOCATIONS |
| | PER 106.3.5.4 FBC. NOTE THERE IS A GENERATOR PANEL NOW |
| | SHOWN ON THE PLAN, THERE WAS NO GENERATOR APPLICATION |
| | OR PERMIT FOR THIS RESIDENCE. |
| | |
| | 2} PER 110.9 AND 110.10: OBTAIN THE |
| | AVAILABLE FAULT CURRENT AT THE UTILITY |
| | AND CALCULATE THE SAME AT THE EQUIPMENT. |
| | INDICATE THE AIC RATING FOR THE |
| | EQUIPMENT IS EQUAL TO OR GREATER THAN |
| | THE AVAILABLE FAULT. |
| | |
| | 3} PROVIDE PANEL SCHEDULES PER 408.4. |
| | |
| | 4}PROVIDE LOAD CALCULATIONS PER ARTICLE 220. INDICATE |
| | WHICH SECTION IS BEING USED. |
| | |
| | 5} RECEPTACLES ARE REQUIRED TO BE GFI PROTECTED IN THE |
| | BATHROOMS PER 210.8(A)(1). SOME ARE MISSING THAT |
| | DESIGNATION ON THE PLAN. |
| | |
| | 6} RECEPTACLES ARE REQUIRED TO BE GFI PROTECTED FOR THE |
| | KITCHENCOUNTERTOPS PER 210.8(A)(6)). |
| | |
| | 7} AT LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT |
| | EACH ISLAND COUNTER SPACE WITH A LONG DIMENSION OF 600 |
| | MM (24 IN.) OR GREATER AND A SHORT DIMENSION OF 300 MM |
| | (12 IN.) OR GREATER. 210.52.(C)(2). |
| | |
| | 8} WET BAR SINKS- WHERE THE RECEPTACLES ARE INSTALLED |
| | TO SERVE THE COUNTERTOP SURFACES AND ARE LOCATED WITHIN |
| | 1.8 M (6 FT) OF THE OUTSIDE EDGE OF THE WET BAR SINK., |
| | GFI PROTECTED 210.8(A)(7). |
| | |
| | 9}SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | |
| | 10} THE DISCONNECTS FOR THE CONDENSING UNITS ARE |
| | MISSING FROM THE PLAN INDICATE LOCATION PER 440.14 AND |
| | CLEARANCE PER 110.26. |
| | |
| | 11} THE ARCHITECTS SEAL IS NOT LEGIBLE ON THE PLAN |
| | 481.221 FAC. |
| | |
| | 12} THERE ARE NO CLOUDS, HIGHLIGHTS OR DELTA 'S ON THE |
| | PLAN TO INDICATE AREAS IF REVISION. PLEASE INCLUDE SAME |
| | PER 106.1.3 FBC. |
| | |