| Notes |
| Date |
Text |
| 2005-07-07 00:00:00 | REVISION DENIED | | | | | | 1) ON SHEET A5 THERE IS AN OPENING WITH | | | ID TAG (T). THERE IS NO SUCH TAG LISTED | | | IN THE WINDOW AND DOOR SCHEDULES ON A9. | | | | | | 2) OPENING #38 IS SHOWN AS A DOUBLE | | | SCREEN DOOR ON A5, BUT IS LISTED IN THE | | | DOOR SCHEDULE AS AN ARCHED FIXED SCREEN. | | | | | | 3) THE ID TAGS FOR OPENINGS 33 AND 34 ON | | | A7 ARE LISTED IN THE DOOR SCHEDULE ON A9 | | | AS ARCHED SWING DOORS. THE REVISED DOORS | | | ARE NOT ARCHED. | | | | | | 4) THE OPENING AT THE GUEST LOGGIA IS | | | SPECIFIED AS SCREEN, BUT A PAIR OF | | | FRENCH DOORS IS SHOWN ON THE ELEVATION | | | ON A7. | | | | | | 5) THE ROOF OF THE CHIMNEY THAT WAS | | | CHANGED TO VENTLESS IS SHOWN FLOATING IN | | | THE AIR ON SHEET A7. | | | | | | 6) SUBMIT THE MANUFACTURER'S | | | SPECIFICATIONS AND LISTING FOR THE | | | VENTLESS FIREPLACE. | | | | | | 7) THE CHIMNEY SHOWN ON A4 AND A6 IS | | | REQUIRED TO EXTEND AT LEAST 3' ABOVE THE | | | HIGHEST POINT WHERE THEY PASS THROUGH | | | THE ROOF PER FBC 2804. | | | | | | 8) ON SHEET S2 THERE ARE TWO BEAM ID | | | TAGS (B16 AND B17) THAT ARE NOT LISTED | | | IN THE BEAM SCHEDULE ON S3. | | | | | | 9) COORDINATE THE OPENING ID TAGS ON A2 | | | WITH THE SCHEDULES ON A9. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | | | | | | | |
|