Plan Review Notes
Plan Review Notes For Permit 04090764
Permit Number 04090764
Review Stop B
Sequence Number 4
Notes
Date Text
2005-07-07 00:00:00REVISION DENIED
  
 1) ON SHEET A5 THERE IS AN OPENING WITH
 ID TAG (T). THERE IS NO SUCH TAG LISTED
 IN THE WINDOW AND DOOR SCHEDULES ON A9.
  
 2) OPENING #38 IS SHOWN AS A DOUBLE
 SCREEN DOOR ON A5, BUT IS LISTED IN THE
 DOOR SCHEDULE AS AN ARCHED FIXED SCREEN.
  
 3) THE ID TAGS FOR OPENINGS 33 AND 34 ON
 A7 ARE LISTED IN THE DOOR SCHEDULE ON A9
 AS ARCHED SWING DOORS. THE REVISED DOORS
 ARE NOT ARCHED.
  
 4) THE OPENING AT THE GUEST LOGGIA IS
 SPECIFIED AS SCREEN, BUT A PAIR OF
 FRENCH DOORS IS SHOWN ON THE ELEVATION
 ON A7.
  
 5) THE ROOF OF THE CHIMNEY THAT WAS
 CHANGED TO VENTLESS IS SHOWN FLOATING IN
 THE AIR ON SHEET A7.
  
 6) SUBMIT THE MANUFACTURER'S
 SPECIFICATIONS AND LISTING FOR THE
 VENTLESS FIREPLACE.
  
 7) THE CHIMNEY SHOWN ON A4 AND A6 IS
 REQUIRED TO EXTEND AT LEAST 3' ABOVE THE
 HIGHEST POINT WHERE THEY PASS THROUGH
 THE ROOF PER FBC 2804.
  
 8) ON SHEET S2 THERE ARE TWO BEAM ID
 TAGS (B16 AND B17) THAT ARE NOT LISTED
 IN THE BEAM SCHEDULE ON S3.
  
 9) COORDINATE THE OPENING ID TAGS ON A2
 WITH THE SCHEDULES ON A9.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  