| Plan Review Notes For Permit 04090764 |
| Permit Number |
04090764 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-01-06 00:00:00 | 1. A.H.U. IN ATTIC AREA MUST CONFORM | | | WITH 2001 FBC/M 306.3 FOR ACCESS AND | | | SERVICE SPACE . | | | 2. THE R/A DUCT FOR LIBARY REFLECT 10" | | | ,SHOULD BE 14". 2001 FBC/M 604.1 | | | BALLANCE RETURN AIR . | | | 3. MASTER BATHROOM 208 REQUIREDS | | | EXHAUST FAN. FBC/M 402.3.1 . | | | 4. PROVIDE MANF. INFORMATION FOR HOOD | | | REFLECTED ON A-7.2 DRAWING 06-02-04 . | | | HOOD COVERS PIZZA OVEN /GRILL /COOKTOP | | | . | | | 5. THERMADOR OUTDOOR COOKTOP MODEL SB2B | | | AND THERMADOR CHAR GLO OUTDOOR BARBECUE | | | ARE LISTED FOR OUTDOOR ONLY . | | | 6.MODEL 60/THE HOME OVED DOES NOT | | | REFLECT MANF. LISTING LOCATION USAGE . | | | PAT RAFTER 561/805/6725 OR 805/6719 . |
|