Plan Review Notes
Plan Review Notes For Permit 04090764
Permit Number 04090764
Review Stop M
Sequence Number 2
Notes
Date Text
2005-01-06 00:00:001. A.H.U. IN ATTIC AREA MUST CONFORM
 WITH 2001 FBC/M 306.3 FOR ACCESS AND
 SERVICE SPACE .
 2. THE R/A DUCT FOR LIBARY REFLECT 10"
 ,SHOULD BE 14". 2001 FBC/M 604.1
 BALLANCE RETURN AIR .
 3. MASTER BATHROOM 208 REQUIREDS
 EXHAUST FAN. FBC/M 402.3.1 .
 4. PROVIDE MANF. INFORMATION FOR HOOD
 REFLECTED ON A-7.2 DRAWING 06-02-04 .
 HOOD COVERS PIZZA OVEN /GRILL /COOKTOP
 .
 5. THERMADOR OUTDOOR COOKTOP MODEL SB2B
 AND THERMADOR CHAR GLO OUTDOOR BARBECUE
 ARE LISTED FOR OUTDOOR ONLY .
 6.MODEL 60/THE HOME OVED DOES NOT
 REFLECT MANF. LISTING LOCATION USAGE .
 PAT RAFTER 561/805/6725 OR 805/6719 .