| Plan Review Notes For Permit 04090764 |
| Permit Number |
04090764 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-01-05 00:00:00 | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE ARCHITECT DID NOT SEAL SHEET | | | E-2. | | | | | | 2} THE GROUNDING SYSTEM AND THE | | | GROUNDING ELECTRODE CONDUCTOR MUST | | | COMPLY WITH 250.50, 250.52,(FOOTER | | | STEEL) AND 250.66 (1/0). | | | | | | 3} THE DISCONNECTS FOR THE CONDENSING | | | UNITS MUST COMPLY WITH | | | 110.26(CLEARANCE) | | | IT DOES NOT APPEAR THIS IS POSSIBLE | | | GIVEN THE PROXIMITY OF THE PRIVECY | | | WALL. | | | | | | 4} THERE ARE FIVE PANELS SHOWN ON THE | | | RISER AND ONLY THREE ON THE PLAN. PLEASE | | | SHOW AND LABEL ALL THE SERVICE | | | EQUIPMENT. | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|