2005-01-05 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE ARCHITECT DID NOT SEAL SHEET
 E-2.
  
 2} THE GROUNDING SYSTEM AND THE
 GROUNDING ELECTRODE CONDUCTOR MUST
 COMPLY WITH 250.50, 250.52,(FOOTER
 STEEL) AND 250.66 (1/0).
  
 3} THE DISCONNECTS FOR THE CONDENSING
 UNITS MUST COMPLY WITH
 110.26(CLEARANCE)
 IT DOES NOT APPEAR THIS IS POSSIBLE
 GIVEN THE PROXIMITY OF THE PRIVECY
 WALL.
  
 4} THERE ARE FIVE PANELS SHOWN ON THE
 RISER AND ONLY THREE ON THE PLAN. PLEASE
 SHOW AND LABEL ALL THE SERVICE
 EQUIPMENT.
  
  