| 2005-01-10 00:00:00 | DENIED |
| | |
| | 1)A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3) THE SAFETY GLAZING IN BATH #2 IS |
| | SPECIFIED FOR THE WRONG WINDOW. PLEASE |
| | CORRECT. |
| | |
| | 4) SUBMIT AN AFFIDAVIT FROM THE ASPHALT |
| | BASED ROOFING PRODUCT MANUFACTURER |
| | CERTIFYING THE USE OF THEIR PRODUCT OVER |
| | AN UNVENTED ATTIC SYSTEM. SEE ATTACHMENT |
| | FROM PALM BEACH COUNTY BCAB. |
| | |
| | 5) SPECIFY THE SCUPPER SIZES FOR |
| | DRAINING THE FLAT ROOFS. |
| | |
| | 6) RISER AND TREAD DIMENSIONS DO NOT |
| | COMPLY WITH FBC 1007.3.1. |
| | |
| | 7) SHOP DRAWING WILL BE REQUIRED FOR THE |
| | FLOOR SYSTEM AT THE SECOND FLOOR. |
| | |
| | 8) ITEM NUMBER (14) FROM THE FIRST |
| | REVIEW STATES THAT BUCK FASTENING |
| | DETAILS ON A10 CONFLICT WITH THOSE ON |
| | S4. THE NOTES ON THE BUCK DETAILS ON A10 |
| | REFER TO S4 FOR DETAILS. THERE WAS NO |
| | SHEET S4 SUBMITTED. |
| | |
| | 9) SUBMIT STRUCTURAL DETAILS FOR |
| | FIREPLACE AND CHIMNEY CONSTRUCTION. |
| | SPECIFY THE REQUIRED HEIGHT OF THE |
| | CHIMNEY ABOVE THE ROOF AND ROOF |
| | STRUCTURES. FBC 2114.3.2 REQUIRES THE |
| | FIREBOX TO HAVE A MINIMUM DEPTH OF 20" |
| | AND A THROAT AT LEAST 8" ABOVE THE |
| | FIREPLACE OPENING. SEE FBC 2114.3.8 FOR |
| | HEARTH DIMENSIONS. |
| | |
| | 10) PRODUCT APPROVALS SUBMITTED |
| | WITH PERMIT APPLICATION AFTER OCTOBER 1, |
| | 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATION PLEASE SEE THE STATE WEBSITE |
| | AT WWW.FLORIDABUILDING.ORG. PRODUCTS |
| | WITH STATEWIDE APPROVAL ARE REQUIRED TO |
| | BE SUBMITTED WITH A COVER SHEET THAT |
| | LISTS THE PRODUCT IDENTITY NUMBER FROM |
| | THE STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. PLEASE |
| | SUBMIT THE COVER SHEETS WITH THE FL |
| | NUMBERS FOR EACH PRODUCT FROM THE STATE |
| | WEBSITE. |
| | |
| | 11) SUBMIT THE FLORIDA PRODUCT APPROVALS |
| | FOR ALL OF THE TRUSS CONNECTORS THAT ARE |
| | SPECIFIED ON THEPLANS. |
| | |
| | 12) SUBMIT STATE OR LOCAL PRODUCT |
| | APPROVALS WITH INSTALLATION INSTRUCTIONS |
| | FOR THE FOLLOWING: |
| | - ACHED TOP CASEMENT WINDOWS |
| | - HOPPER WINDOWS |
| | |
| | 13) THE PRODUCT APPROVAL THAT WAS |
| | SUBMITTED FOR THE SLIDING GLASS DOOR HAS |
| | ONLY SMALL MISSLE IMPACT RATING AND WILL |
| | BE REQUIRED TO BE COVERED BY STORM |
| | PANELS. SUBMIT STORM PANEL PRODUCT |
| | APPROVAL KEY PLAN AND INSTALLATION |
| | INSTRUCTIONS. |
| | |
| | |