| Notes |
| Date |
Text |
| 2004-10-25 00:00:00 | DENIED: | | | 1.PLEASE PROVIDE MANUAL J CALUCALTIONS | | | PER 2001 FBC CHAPTER 13 SUB-CHAPTER 6 | | | SECTION 607.1.ABC.1. | | | | | | 2.AUXILIARY DRAIN PAN WITH OVERFLOW | | | PROTECTION REQUIRED PER 2001 FBC(M) | | | 307.2.3. | | | | | | 3.PROVIDE ADDITIONAL INFORMATION ON | | | THE PIZZA OVEN, GRIDDLE AND 2 BURNER | | | STOVE IN THE LANAI AREA.WILL THESE | | | APPLIANCES BE GAS OR ELECTRIC?PROVIDE | | | MANUFACTURER SUBMITTAL DATA AND VENTING | | | INFORMATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|